Name
Range
Step
Description
U0> Pick-up
setting
0.0...1 000 000V
0.1V
The required residual voltage on the primary side for the relay to trip.
Detected U0/
I0 angle (fi)
-360.00...360.00deg
0.01deg
The angle in degrees between the monitored residual voltage and the
current.
I0 Magnitude
0.000...250.000×I0
n
0.001×I0
n
The per-unit-value of the monitored residual current.
I0 Wattmetric
I0xCos(fi)
-250.000...250.000×I0
n
0.001×I0
n
The wattmetric per-unit-value of the monitored residual current.
I0 Varmetric
I0xSin(fi)
-250.000...250.000×I0
n
0.001×I0
n
The varmetric per-unit-value of the monitored residual current.
I0 direction
now
0: Undefined
1: Forward
2: Reverse
-
The detected direction of the residual current.
I0 meas/ I0
set now
-250.000...250.000×I0
n
0.001×I0
n
The ratio between the monitored residual current and the pick-up
value.
U0
measurement
now
0.000...500.000%U0
n
0.001%U0
n
The measured voltage in the chosen voltage channel.
Expected
operating
time
0.000...1800.000s
0.005s
Displays the expected operating time when a fault occurs. When
IDMT mode is used, the expected operating time depends on the
measured current value. If the measured current changes during a
fault, the expected operating time changes accordingly.
Time
remaining to
trip
-1800.000...1800.000s
0.005s
When the function has detected a fault and counts down time
towards a trip, this displays how much time is left before tripping
occurs.
Function blocking
The block signal is checked in the beginning of each program cycle. The blocking signal is received
from the blocking matrix in the function's dedicated input. Additionally, the directional earth fault
protection function includes an internal inrush harmonic blocking option which is applied according to
the parameters set by the user. If the blocking signal is not activated when the pick-up element
activates, a START signal is generated and the function proceeds to the time characteristics
calculation.
Table. 5.3.5 - 73. Internal inrush harmonic blocking settings.
Name
Description
Range
Step
Default
Inrush harmonic blocking (internal-
only trip)
Enables and disables the 2
nd
harmonic
blocking.
0: No
1: Yes
-
0: No
2
nd
harmonic blocking limit (Iharm/
Ifund)
The 2
nd
harmonic blocking limit.
0.10…50.00%I
fund
0.01%I
fund
0.01%I
fund
If the blocking signal is active when the pick-up element activates, a BLOCKED signal is generated and
the function does not process the situation further. If the START function has been activated before the
blocking signal, it resets and the release time characteristics are processed similarly to when the pick-
up signal is reset.
The blocking of the function causes an HMI display event and a time-stamped blocking event with
information of the startup current values and its fault type to be issued.
The blocking signal can also be tested in the commissioning phase by a software switch signal when
the relay's testing mode "Enable stage forcing" is activated (
General
→
Device).
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
124
Содержание AQ-M215
Страница 1: ...AQ M215 Motor protection IED Instruction manual ...
Страница 410: ...Figure 7 4 242 Example block scheme A AQ Q M215 M215 Instruction manual Version 2 04 409 ...
Страница 432: ...Figure 8 14 265 Panel cutout dimensions and device spacing A AQ Q M215 M215 Instruction manual Version 2 04 431 ...
Страница 466: ...10 Ordering information A AQ Q M215 M215 Instruction manual Version 2 04 465 ...