9.1.3.4 Milliampere module (mA out & mA in)
Table. 9.1.3.4 - 304. Technical data for the milliampere module.
Signals
Output magnitudes
Input magnitudes
4 × mA output signal (DC)
1 × mA input signal (DC)
mA input
Range (hardware)
Range (measurement)
Inaccuracy
0...33 mA
0...24 mA
±0.1 mA
Update cycle
Response time @ 5 ms cycle
Update cycle time inaccuracy
5...10 000 ms, setting step 5 ms
~ 15 ms (13...18 ms)
Max. +20 ms above the set cycle
mA input scaling range
Output scaling range
0...4000 mA
-1 000 000.0000…1 000 000.0000, setting step 0.0001
mA output
Inaccuracy @ 0...24 mA
±0.01 mA
Response time @ 5 ms cycle [fixed]
< 5 ms
mA output scaling range
Source signal scaling range
0...24 mA, setting step 0.001 mA
-1 000 000.000…1 000 000.0000, setting step 0.0001
9.1.3.5 RTD input module
Table. 9.1.3.5 - 305. Technical data for the RTD input module.
Channels 1-8
2/3/4-wire RTD and thermocouple sensors
Pt100 or Pt1000
Type K, Type J, Type T and Type S
Channels 7 & 8 support mA measurement
9.1.3.6 RS-232 & serial fiber communication module
Table. 9.1.3.6 - 306. Technical data for the RS-232 & serial fiber communication module.
Ports
RS-232
Serial fiber (GG/PP/GP/PG)
Serial port wavelength
660 nm
Cable type
1 mm plastic fiber
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
439
Содержание AQ-M215
Страница 1: ...AQ M215 Motor protection IED Instruction manual ...
Страница 410: ...Figure 7 4 242 Example block scheme A AQ Q M215 M215 Instruction manual Version 2 04 409 ...
Страница 432: ...Figure 8 14 265 Panel cutout dimensions and device spacing A AQ Q M215 M215 Instruction manual Version 2 04 431 ...
Страница 466: ...10 Ordering information A AQ Q M215 M215 Instruction manual Version 2 04 465 ...