9.1.1.3 Frequency measurement
Table. 9.1.1.3 - 290. Frequency measurement accuracy.
Frequency measurement performance
Frequency measuring range
6…75 Hz fundamental, up to the 31
st
harmonic current or voltage
Inaccuracy
10 mHz
9.1.2 CPU & Power supply
9.1.2.1 Auxiliary voltage
Table. 9.1.2.1 - 291. Power supply model A
Rated values
Rated auxiliary voltage
85…265 V (AC/DC)
Power consumption
< 7 W
< 15 W
Maximum permitted interrupt time
< 60 ms with 110 VDC
DC ripple
< 15 %
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
Table. 9.1.2.1 - 292. Power supply model B
Rated values
Rated auxiliary voltage
18…72 VDC
Power consumption
< 7 W
< 15 W
Maximum permitted interrupt time
< 90 ms with 24 VDC
DC ripple
< 15 %
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
9.1.2.2 CPU communication ports
Table. 9.1.2.2 - 293. Front panel local communication port.
Port
Port media
Copper Ethernet RJ-45
Number of ports
1
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
434
Содержание AQ-M215
Страница 1: ...AQ M215 Motor protection IED Instruction manual ...
Страница 410: ...Figure 7 4 242 Example block scheme A AQ Q M215 M215 Instruction manual Version 2 04 409 ...
Страница 432: ...Figure 8 14 265 Panel cutout dimensions and device spacing A AQ Q M215 M215 Instruction manual Version 2 04 431 ...
Страница 466: ...10 Ordering information A AQ Q M215 M215 Instruction manual Version 2 04 465 ...