Figure. 4.4 - 13. Registers.
Register menu content is not available in the HMI. It can only be accessed with AQtivate setting tool.
Stored in the "Registers" section you can find both "Operation event register" and "General event
register".
"Operation event register" stores the function's specific fault data. There are twelve (12) registers, and
each of them includes data like the pre-fault value, the fault value, the time stamp and the active group
during the trigger. Data included in the register depend on the protection function. You can clear the
the operation register by choosing "Clear registers"
→
"Clear".
"General event register" stores the event generated by the stage. These general event registers cannot
be cleared.
A
AQ
Q-M215
-M215
Instruction manual
Version: 2.04
22