Using the APP Recorder
6-10
6.
Flash:
Using Flash has a very limited application. If you would like to use Flash for Data, please
consult APP Engineering Inc., before setting up the use of Flash.
7.
(Required)
Next to the
Setup Path
box, click the
to specify the location of files such as the
Point Assignment Record, calibration factors, Line Group Record, trace files, and diagnostic
record. By default, the factory creates the path
{C:,D:}\APP Recorder\Setup.
You can change
this value to any other path you want. However, you should not change the path without
understanding how the APP Recorder runs. Incorrectly changing the path can prevent the APP
Recorder from running.
8.
In the
Max #Faults in FSum:
box,
specify the number of Fault record IDs included in the Fault
Summary upload to the master station (i.e. remote APP ClearView), when a Fault Summary file is
created. The larger the number, the longer it takes to get the summary file. Typically, a reasonable
number for this “fast” retrievable file is between 50 and 500.
Note
: The APP Recorder Program AND APP Clearview Program should be configured to share
the same Data folder (i.e. {C:,D:}\APP Recorder\Data). All Fault records are available to
APP Clearview with this configuration.
9.
After normal communication has been established between the APP ClearView and the APP
Recorder programs, the ideal disconnect situation is for someone at the master station or someone
at the APP Recorder to initiate a disconnect or hang up command. When this is done, both
programs are aware of the disconnect request and can properly close down communications.
However, it is possible for a communication path to be cut without notice. This results in neither
program receiving notice of disconnect. Therefore, a hang up timer is needed to ensure that both
programs receive an automatic command to release the communications link.
The default hang up timer for both the APP Recorder and APP ClearView programs is 10 minutes.
However, the APP Recorder hang up timer has a delay that makes its effective default time 10
minutes and 30 seconds. Therefore, in the case of no communications activity, the APP ClearView
program will be the first to initiate a hang up action.
Do you want to make the APP Recorder the first program to initiate a hang up action in the event
of an unexpected disconnect?
If
yes
, then in the
Hang up if connection to ClearView has been idle for X minutes
box, type a value less than 10 minutes.
If
no
, skip to the next step.
10.
Have you already set up dial-up networking for the APP Recorder?
If
yes
, then select the
Dial-up Networking
has been setup check box. See
for instructions on setting up dial-up networking.
If
no
, skip to the next step.
11.
If you want Point Assignment Record and Line Group Record saved with Transient Record, click
the check box:
Save .par and .lgp with Transient Record
.
12.
If you want the Transient Alarm triggered during a Test Run, click the check box:
Turn
Transient Alarm on during Test Run
.
Note:
The Transient Alarm has to be mapped in the Point Assignment, General Settings Tab for
the alarm to be turned on.
Содержание APP-601
Страница 1: ...APP 601 Recorder Operating Manual...
Страница 15: ...Introduction 1 1 1 Introduction...
Страница 18: ...2 1 2 Specifications...
Страница 25: ...Installation Overview 3 1 3 Installation Overview...
Страница 38: ...Hardware 4 1 4 Hardware...
Страница 61: ...Installing the Recorder Software 5 1 5 Installing the Recorder Software...
Страница 67: ...Using the APP Recorder 6 1 6 Using the APP Recorder...
Страница 117: ...Using the APP Recorder 6 51...
Страница 124: ...Using the APP Driver 7 1 7 Using the APP Driver...
Страница 128: ...Using the OScope 8 1 8 Using the OScope...
Страница 139: ...Other Information 9 1 9 Other Information...