SECTION 6 – TEST AND PLACE IN SERVICE
2014-APR-30 REV. 0 PAGE 6-7
CHECKFIRE 110
Detection and Actuation System
TABLE 6-4: OPERATIONAL TEST (Continued)
Release Circuit - Supervision Test
Remove RCT from the Release Circuit. The CHECKFIRE
110 Control Module indicates the following.
1. Release Fault LED pulses AMBER 1 x 10 seconds.
2. Sounder pulses 1 x 10 seconds.
Test silence function; push the “DELAY/Reset/Silence”
button.
3. Sounder silences and Release Fault LED continues to
pulse AMBER 1 x 10 seconds.
Reconnect RCT to release circuit.
4. CHECKFIRE 110 Control Module returns to Normal
status; Power LED is GREEN steady-on.
009180
RECONNECT RCT
MODuLE
RETuRNS TO
NORMAL STATuS
POWER LED
IS GREEN
STEADY-ON
009180b
RELEASE FAULT
INDICATION
(RCT REmOVED)
AMBER LED AND
SOuNDER PuLSE
1 x 10 SECONDS
!
009180b
SILENCE FUNCTION
RELEASE FAULT
INDICATION
PuSH TO
SILENCE
SOuNDER (LED
CONTINuES)
AMBER LED
PuLSES 1 x 10
SECONDS
!