SECTION 8 – RECHARGE, INSPECTION, AND MAINTENANCE
PAGE 8-2 REV. 01 2014-MAY-01
RECHARGE (Continued)
c. Examine actuating end of PAD to determine if PAD has
actuated. Note: Occasionally the actuating pin will pull
back into the PAD. Look directly at actuating end where
pin extends. If pin is visible PAD has actuated. See
Figure 8-2.
d. If PAD actuated, remove PAD from the connector and
discard. See Figure 8-1. Do not install new PAD until
testing is complete, see Step 10. Find and discard
small brass disk ejected from actuating end of PAD
during release.
e. If PAD has not actuated (system actuated with optional
pneumatic manual actuator), refer to Five-Year PAD
Replacement instructions, page 8-7, and replace if
needed.
FIGURE 8-1
ACTUATED PAD
009242
FIGURE 8-2
CHECK END OF PAD
009243
f. If needed, remove 1/4 in. gas actuation hose(s). Loosen
and slide base of Electric-Pneumatic Actuator sideways
to remove from each expellant gas cartridge.
CAUTION
If Electric-Pneumatic Actuator is difficult to remove
puncture pin is not fully retracted. Do not force.
g. Disassemble actuator and inspect for damage. Using
small wood dowel gently push puncture pin and spring
out of body being careful not to bend puncture pin.
Retain all parts for re-assembly. See Figure 8-3.
FIGURE 8-3
ELECTRIC-PNEUMATIC ACTUATOR
009244
h. Inspect and replace all damaged components (i.e.
o-rings, flat gaskets, etc.).
i. Lubricate all o-rings and gaskets with Dow Corning #4
(or equal) and reinstall. Include o-ring on PAD.
j. Replace flat gasket semi-annually.
k. Install spring on puncture pin and insert into body. Push
down several times to confirm ease of movement.
l. Reassemble actuator.
m. Install actuator cap and pressure test using dry air or
nitrogen.
7. Recharge the fire suppression system in accordance
with the appropriate A-101 or LVS Design, Installation,
Recharge and Maintenance manual (latest edition).
LT-A-101-10/20/30 Manual
(Part No. 24327)
LT-A-101-50/125/250 Manual (Part No. 427865)
LVS Manual
(Part No. 427109)
8. After fire suppression system recharge is complete:
a. Confirm puncture pin is completely retracted on the
Electric-Pneumatic Actuator. See Figure 8-4.
WARNING
!
Before attaching Electric-Pneumatic Actuator to expel-
lant gas cartridge, verify the cartridge is properly
secured and confirm actuator puncture pin is in
the completely retracted position. If puncture pin is
not completely retracted the cartridge seal can become
damaged or pierced which can result in system actua-
tion or serious personal injury or death.
CHECKFIRE 110
Detection and Actuation System
RELEASE
CIRCUIT
DROP CABLE
CONNECTOR
PAD O-RING
REMOVE
ACTUATED PAD
IF PIN IS VISIBLE
PAD HAS
ACTUATED
Содержание CHECKFIRE 110
Страница 2: ......
Страница 6: ...REVISION RECORD PAGE 2 REV 0 2014 MAY 01 NOTES CHECKFIRE 110 Detection and Actuation System ...
Страница 22: ...SECTION 3 USER INTERFACE PAGE 3 4 REV 0 2014 APR 30 NOTES CHECKFIRE 110 Detection and Actuation System ...
Страница 68: ...SECTION 7 IN CASE OF FIRE PAGE 7 2 REV 0 2014 APR 30 NOTES CHECKFIRE 110 Detection and Actuation System ...
Страница 84: ...SECTION 9 TROUBLESHOOTING PAGE 9 10 REV 0 2014 APR 30 NOTES CHECKFIRE 110 Detection and Actuation System ...