SECTION 6 – TEST AND PLACE IN SERVICE
2014-APR-30 REV. 0 PAGE 6-9
CHECKFIRE 110
Detection and Actuation System
TABLE 6-4: OPERATIONAL TEST (Continued)
Detection Circuit: Alarm Condition Test
CAUTION
Before beginning this test, verify:
• Release circuit test Plug(s) and Rct are connected in the
Release Circuit.
• Dct replaces the EoL Device in the Detection circuit.
1. Simulate alarm condition by turning switch on DCT to
ALARM position.
2. Verify accuracy of time delay:
a. 15-Second Time Delay: The “PuSH to Activate /
Alarm When Lit” RED LED and Sounder pulse 2 x 1
second until last 5 seconds of time delay period.
5 seconds before end of 15-second time delay period,
pulse rate increases to 4 x 1 second.
b. 5-Second Time Delay: The “PuSH to Activate / Alarm
When Lit” RED LED and Sounder pulse 4 x 1 second.
3. Release Circuit Activation: upon expiration of the time
delay, the Release Circuit activates.
4. Release Activated: The “PuSH to Activate / Alarm
When Lit” RED LED and Sounder remain steady-on for
10 seconds.
5. Post Release Activated: The RED “PuSH to Activate /
Alarm When Lit” LED and Sounder pulse 1 x 10 seconds.
6. Push “DELAY/Reset/Silence” button to test Sounder
silence.
7. RED LED continues to pulse 1 x 10 seconds.
8. confirm Rct displays “PASS.”
009180d
RELEASE ACTIVATED
RED LED AND SOuNDER
REMAIN STEADY-ON
FOR 10 SECONDS
009180c_RED
CAUTION
VERIFY RCT AND DCT
INSTALLED!
START OF DETECTION
CIRCUIT ALARm
CONDITION
(DCT = ALARm)
RED LED AND
SOuNDER PuLSE
2 x 1 SEC. FOR
10 SECONDS
(15 SECOND TIME
DELAY ONLY)
5 SECONDS BEFORE
END, RED LED AND
SOuNDER PuLSE
4 x 1 SEC. FOR
5 SECONDS
(NOTE: 5 SECOND TIME
DELAY STARTS AT THIS
LEVEL)
009180b
POST RELEASE
ACTIVATED
RED LED AND
SOuNDER PuLSE
1 x 10 SECONDS
PuSH TO SILENCE
SOuNDER
(LEDs CONTINuE)
Содержание CHECKFIRE 110
Страница 2: ......
Страница 6: ...REVISION RECORD PAGE 2 REV 0 2014 MAY 01 NOTES CHECKFIRE 110 Detection and Actuation System ...
Страница 22: ...SECTION 3 USER INTERFACE PAGE 3 4 REV 0 2014 APR 30 NOTES CHECKFIRE 110 Detection and Actuation System ...
Страница 68: ...SECTION 7 IN CASE OF FIRE PAGE 7 2 REV 0 2014 APR 30 NOTES CHECKFIRE 110 Detection and Actuation System ...
Страница 84: ...SECTION 9 TROUBLESHOOTING PAGE 9 10 REV 0 2014 APR 30 NOTES CHECKFIRE 110 Detection and Actuation System ...