SECTION 6 – TEST AND PLACE IN SERVICE
2014-APR-30 REV. 0 PAGE 6-13
CHECKFIRE 110
Detection and Actuation System
TABLE 6-4: OPERATIONAL TEST (Continued)
Field Test Spot Thermal Detectors (Continued)
To test the functionality of the Spot Thermal Detector:
1. Disable the fire suppression system by disconnecting the
Release Circuit Cable from the Release Circuit Lead on
the control module. (CHECKFIRE Control Module will
display a Release Circuit Fault.)
CAUTION
Disconnecting the Release circuit will disable the fire
suppression system. The system will not be able to
actuate the Release circuit in the event of a fire. Second
-
ary fire suppression measures should be implemented
before disabling the system.
2. Ensure the heat gun is properly connected per the manu-
facturer’s recommendations and turn it on. the applied
temperature for the 250 °F (121 °C) detector should not
exceed 400 °F (204 °C), and the applied temperature for
the 350 °F (176.6 °C) detector should not exceed 500 °F
(260 °C).
3. Position the tip of the heat gun as close to the detector
head as possible and begin applying heat to the unit. The
direction of the applied heat should be as perpendicular
to the face of the detector head as possible.
4. Continue to apply heat to the detector head until contact
closure occurs. An audible click should be heard from the
detector head and the CHECKFIRE 110 Control Module
should go into alarm. Note: Reaction times between
detectors will vary. Air movement in the vicinity of the
detectors should be minimized to the greatest extent
possible. Excessive air movement will affect heat transfer
to the detector which may extend activation times.
5. As soon as contact closure occurs, immediately and
carefully remove the tip of the heat gun from the detec-
tor head. Note: Detector will remain in alarm for several
seconds before contacts re-open.
6. Allow the control module to complete the alarm and
release cycle then reset control module after the detector
has cooled enough for the contacts to re-open. (Reset
control module to Normal: Press and hold the “DELAY/
Reset/Silence” button for 3 seconds; Power LED and
Sounder quickly pulse 3 or 5 times, then Power LED
remains GREEN steady-on.) Release circuit fault will
continue.
7. Repeat Steps 2–6 for each detector that requires testing.
8. Once all detectors have been tested and contacts are
re-opened, the detection system should be returned to
normal operation (see step 6). Reconnect Release Circuit
Cable to control module Release Circuit Lead.
SPOT THERMAL
DETECTOR
HEAT GuN
APPLY PERPENDICULAR TO DETECTOR FACE
009245
Содержание CHECKFIRE 110
Страница 2: ......
Страница 6: ...REVISION RECORD PAGE 2 REV 0 2014 MAY 01 NOTES CHECKFIRE 110 Detection and Actuation System ...
Страница 22: ...SECTION 3 USER INTERFACE PAGE 3 4 REV 0 2014 APR 30 NOTES CHECKFIRE 110 Detection and Actuation System ...
Страница 68: ...SECTION 7 IN CASE OF FIRE PAGE 7 2 REV 0 2014 APR 30 NOTES CHECKFIRE 110 Detection and Actuation System ...
Страница 84: ...SECTION 9 TROUBLESHOOTING PAGE 9 10 REV 0 2014 APR 30 NOTES CHECKFIRE 110 Detection and Actuation System ...