![Ansul CHECKFIRE 110 Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/ansul/checkfire-110/checkfire-110_planning-installation-operation-and-maintenance-manual_2946332063.webp)
SECTION 6 – TEST AND PLACE IN SERVICE
2014-MAY-01 REV. 01 PAGE 6-15
CHECKFIRE 110
Detection and Actuation System
“PUSH To Activate / Alarm when Lit” LED
and Sounder Indications
manual Action
(Release Circuit Activation)
2 x 1 sec.
for 10 sec.
4 x 1 sec.
for 5 sec.
Steady-on
for 10 sec.
1 x 10 sec.
until reset*
Push the “PuSH to Activate / Alarm When Lit” button
Or: Pull ring pin and push an EMA
(Immediate release for either action)
Post discharge
Detection Circuit Input
15-Second Time Delay (1st 10 seconds)
5-Second Time Delay
And 5 Seconds to release for 15 Second Time Delay
Release Circuit Activation
(Time Delay Expired)
Post discharge
TABLE 6-5: SUmmARY ALARm CONDITION INDICATORS
Disconnect external power circuit connection at the
CHECKFIRE 110 Power Circuit Lead.
1. Power LED pulses AMBER 1 x 30 seconds.
2. Sounder pulses 1 x 30 seconds for 10 minutes then
auto-silences to conserve energy. Do not wait for auto-si-
lence to begin, move to next step.
3. Push the “DELAY/Reset/Silence” button to test Sounder
silence. The LED continues to pulse 1 x 30 seconds.
4. Repeat the following tests (pages 6-9 thru 6-13) with
control module on internal power:
• Detection circuit: Alarm condition test
• Detection circuit: test time Delay Restart
• field test Spot thermal Detectors
• Manual Activation Release circuit test
• Electric Manual Actuator (EMA) test
Note: For above tests the Power LED continues to pulse
AMBER 1 x 30 seconds.
TABLE 6-6: INTERNAL POwER CIRCUIT – OPERATIONAL TEST
009180b
INTERNAL POwER
TESTING (REmOVE
POwER CABLE)
AMBER POWER
LED AND
SOuNDER PuLSE
1 x 30 SECONDS
PuSH TO SILENCE
SOuNDER (LED
CONTINuES)
REPEAT TESTS
PAgES 6-9 – 6-13
ON INTERNAL
POWER
* Release Fault Indicator also pulses at this rate during post discharge. When release circuit test device is installed,
Release Fault Indicator does not pulse.
Содержание CHECKFIRE 110
Страница 2: ......
Страница 6: ...REVISION RECORD PAGE 2 REV 0 2014 MAY 01 NOTES CHECKFIRE 110 Detection and Actuation System ...
Страница 22: ...SECTION 3 USER INTERFACE PAGE 3 4 REV 0 2014 APR 30 NOTES CHECKFIRE 110 Detection and Actuation System ...
Страница 68: ...SECTION 7 IN CASE OF FIRE PAGE 7 2 REV 0 2014 APR 30 NOTES CHECKFIRE 110 Detection and Actuation System ...
Страница 84: ...SECTION 9 TROUBLESHOOTING PAGE 9 10 REV 0 2014 APR 30 NOTES CHECKFIRE 110 Detection and Actuation System ...