Issue 2 14/07/16
75
Appendix 10
10 Appendix
10.1 HIflo auto ignition “G” series addendum
10.2 Specifications
10.1.1 Features of Honeywell integrated controls
system
• Attractive digital water heater display on control panel for
setting and displaying the temperature setpoint. Pressing
temperature up and down buttons changes the temperature
setpoint. Temperature format may be displayed in degrees F
or degrees C.
• Single control board with plug in wiring controls temperature,
ignition, and flue damper operation.
• Reduced number of parts for servicing and wiring.
• Plug in wiring reduces chance of miswiring.
• Water heater display will show diagnostic codes in the event
the water heater needs servicing. Aids in diagnosing and
servicing the water heater.
• Water heater display can show up to 10 previous error codes
in the service mode to further aid in servicing the water
heater.
Power Supply
Dedicated 120 VAC, 60 Hz., 15 A
Current Draw
Less than 5 Amps.
Gas Supply Connection
25mm NPT connection to gas valve for 370,000 Btu/hr. and over for natural gas, 19mm NPT
for
rest. Schedule 40 black iron pipe recommended.
Approved Gas Type
Natural or Propane. Gas supply must match the gas type listed on the water heater rating
label.
Minimum Clearance for Servicing 610mm Front Clearance, 508mm Top, 152mm Sides.
Maximum Water Supply Pressure 150 PSI.
Thermostat Sensor(s)
Redundant thermistor with 11,900 + or - 0.5% ohms resistance at 21°C. Sensor inside
well for lower sensor. Some models use an additional upper sensor (w/o well) with same
resistance values.
Control Board
Honeywell Integrated Control Board for Temperature Control, Flue Damper, and Ignition
Control Functions. Operates on 24 volts AC current from transformer. Some models use
single sensor boards, others use two sensors.
Control Display
Honeywell LCD Control Display with Temperature Setpoint, Format, and Error Code Display
in User Mode, Diagnostic Functions in Service Mode. Communicates with Control Board.
Transformer
120 VAC Primary, 24 VAC Secondary, 40 VA.
Pilot
Intermittent Pilot with Spark Electrode and Flame Sensor monitored by Control Board.
Flue Damper
24 VAC, 60 Hz., 80 Ma.
Содержание 24/39
Страница 1: ......
Страница 65: ...Issue 2 14 07 16 65 Parts List and Illustrations 9 9 10 HIflo models 62 341 and 54 418 440 Natural Gas Fig 34 ...
Страница 69: ...Issue 2 14 07 16 69 Parts List and Illustrations 9 9 15 HIflo LPG models L62 309 L54 399 Fig 31 ...
Страница 112: ...112 Issue 2 14 07 16 ...
Страница 113: ...Issue 2 14 07 16 113 ...
Страница 114: ...114 Issue 2 14 07 16 ...