Issue 2 14/07/16
29
Installation
3
6. Fit earth strap to 11⁄2BSP sq.tee optional hot outlet
connection. Connect earth return at this point. Cut lead to
required length and use spade terminal provided.
7. Connect potentiostat mains input cable to a permanent 240V
electrical supply via an unswitched spur outlet (fuse rating 3
Amps).
3.9.5 Test the installation
1. Refill the water heater and check for leaks.
2. Switch on electrical supply to correx powered anode.
3. The green control lamp on the potentiostat indicates that the
installation is functioning correctly.
4. The red control lamp on the potentiostat indicates a fault.
Switch off electrical supply before any repair work is carried
out.
The installation is now complete.
3.9.6 Unvented systems, standard range
Unvented Systems should be fitted by an Approved Installer
When used in an unvented system, the Andrews Water Heater
will supply hot water at a pressure of 3.5bar provided that this
pressure is available at the mains feed. During conditions of no-
flow, system pressure may rise to a maximum of 6bar whilst the
burner is operating. When testing the system, it is
recommended that a maximum test pressure of 8bar is
employed.
Fig. 10
The heater can be used on unvented hot water storage
systems, with the addition of an Unvented Systems Kit, part
number B171 available from Andrews Water Heaters.
Item D4 must be fitted into the temperature relief port in the
water heater tank. D6 Adaptor - For use with D4 on heater
models 40/61 63/62 & 84/87.
When assembling items D1 and D2, ensure that the flow arrows
marked on the components are pointing in the direction of flow
i.e. towards the water heater.
The cold water for services may be drawn from the 22mm
compression port on item D1 (a). The water pressure at this
point will be similar to that available at the hot water outlet of the
water heater. If port (a) is not used, it should be sealed with the
blanking plug supplied.
If higher flow rates are required for the cold water services, a
suitable tee fitting should be fitted to the pipework, upstream of
item D1.
See
See Parts List Page 56. The Wall Mounting Kit is
available as an optional extra.
Fig. 10
D3 expansion
vessel
D4 temperature/
pressure relief
valve
D6
D5 tundish
Cold water feed
D7 hose
assembly
(a)
Cold water
inlet of
water
heater
D2 check valve/
expansion valve
D1 pressure
reducing
valve/
strainer
Balanced
cold water
take-off
(if required)
Содержание 24/39
Страница 1: ......
Страница 65: ...Issue 2 14 07 16 65 Parts List and Illustrations 9 9 10 HIflo models 62 341 and 54 418 440 Natural Gas Fig 34 ...
Страница 69: ...Issue 2 14 07 16 69 Parts List and Illustrations 9 9 15 HIflo LPG models L62 309 L54 399 Fig 31 ...
Страница 112: ...112 Issue 2 14 07 16 ...
Страница 113: ...Issue 2 14 07 16 113 ...
Страница 114: ...114 Issue 2 14 07 16 ...