18
Issue 2 14/07/16
3
Installation
3.5 Electrical supply - Auto ignition units
3.5.1 Standard Range models - Hiflo models
External wiring to the water heater(s) must be installed in
accordance with current I.E.E. Regulations for the wiring of
buildings and to any Local Regulations that may apply.
The Auto Ignition Heater is designed to operate from a
220/240V, Single Phase supply. The fuse rating is 5 amps.
The method of connection to the mains electricity supply should
facilitate complete electrical isolation of the appliance, preferably
by use of an unswitched shuttered socket outlet in conjunction
with a fused three pin plug, both complying with the
requirements of BS 1363.
Alternatively, a fused double pole switch or fused spur box
serving only the heater may be used.
The point of connection to the mains electricity supply should be
readily accessible and adjacent to the appliance.
Fig 3a and 3b.
Connect the electrical supply to the main control panel terminal
block via the cable glands in the base of the control panel.
Mains input cable should be 0.75mm
2
, 3 core, and should be
connected to the mains supply as detailed above.
It is recommended that screen cable is used where the volt-free
contacts are to be connected from an external supply. This will
eliminate the risk of possible interference from nearby high
voltage cables.
Data sheets available for Hiflo and Standard Range, Automatic
Ignition Control System. Contact Andrews Water Heaters.
Содержание 24/39
Страница 1: ......
Страница 65: ...Issue 2 14 07 16 65 Parts List and Illustrations 9 9 10 HIflo models 62 341 and 54 418 440 Natural Gas Fig 34 ...
Страница 69: ...Issue 2 14 07 16 69 Parts List and Illustrations 9 9 15 HIflo LPG models L62 309 L54 399 Fig 31 ...
Страница 112: ...112 Issue 2 14 07 16 ...
Страница 113: ...Issue 2 14 07 16 113 ...
Страница 114: ...114 Issue 2 14 07 16 ...