Installation
3.9.8 Unvented systems, HIflo range
Unvented Systems should be fitted by an Approved Installer
When used in an unvented system, the Andrews Water Heater
will supply hot water at a pressure of 3.5bar provided that this
pressure is available at the mains feed. During conditions of no-
flow, system pressure may rise to a maximum of 6bar whilst the
burner is operating. When testing the system, it is
recommended that a maximum test pressure of 8bar is
employed.
Fig. 17
The heater can be used on unvented hot water storage
systems, with the addition of an Unvented Systems Kit, part
number B290 available from Andrews Water Heaters.
Item C4 must be fitted into the temperature relief port in the
water heater tank.
When assembling items C1 and C2, ensure that the flow arrows
marked on the components are pointing in the direction of flow
i.e. towards the water heater.
The cold water for services may be drawn from the 22mm
compression port on item C1 (a). The water pressure at this
point will be similar to that available at the hot water outlet of the
water heater. If port (a) is not used, it should be sealed with the
blanking plug supplied.
If higher flow rates are required for the cold water services, a
suitable tee fitting should be fitted to the pipework, upstream of
item C1.
The pipework fitted to the tundish outlet should be at least
28mm diameter and should be terminated at a suitable drain.
All fittings and materials must be suitable for use with drinking
water and listed in the current Water Research Centre
"Materials and Fittings Directory".
Installation of unvented hot storage water systems must comply
with Part G of Schedule 1 of the Building Regulations.
Typical water service layout for HIflo Range single heater
unvented system is shown in Fig 18.
Typical water service layouts for HIflo Range multiple
heater unvented systems are shown in Figs 19 and 20.
See
See Parts List Page 60. The Wall Mounting Assembly is
available as an optional extra.
See
See Building Regulations 1991 Approved Document G3.
Fig. 17
Fig. 18
C3
C4 temperature/
pressure relief
valve
C5 tundish
NB. Tees, elbows, stop valve and pipework not supplied
Cold water inlet
OPTIONAL PARTS
C7 hose
assembly
(a)
Cold water
inlet of water
heater
C2 check valve/
C6 expansion valve
C1 pressure
reducing
valve/
strainer
Balanced
cold water
take-off
(if required)
Roof
1.0m
Split flue clip
Split flue clip
To drain
To drain
Cold water
take-off
Cold water
take-off
Cold
water
inlet
Cold
water
inlet
Hot water
service
Hot
water
service
Return via tee
Return via tee
Terminal (away from any
obstructions or any openings
or features that may allow
products re-entry into the
building).
Top Entry Models
65/173
81/264
Front Entry
All Models
Содержание 24/39
Страница 1: ......
Страница 65: ...Issue 2 14 07 16 65 Parts List and Illustrations 9 9 10 HIflo models 62 341 and 54 418 440 Natural Gas Fig 34 ...
Страница 69: ...Issue 2 14 07 16 69 Parts List and Illustrations 9 9 15 HIflo LPG models L62 309 L54 399 Fig 31 ...
Страница 112: ...112 Issue 2 14 07 16 ...
Страница 113: ...Issue 2 14 07 16 113 ...
Страница 114: ...114 Issue 2 14 07 16 ...