40
Issue 2 14/07/16
4
Commissioning
4.4 HIflo Range Auto ignition models
4.4.1 Lighting the burner
1. Ensure gas supply is ON.
2. Turn gas control knob to ON position.
3. Using control thermostat, select required water temperature.
4. Move electrical ON/OFF switch to ON. After a delay of about
10 seconds, the burner will light.
5. Check pilot and main gas connections at gas control valve
using leak detection fluid whilst burner is alight. Turn off, seal
any leakages, then re-test.
4.4.2 Shutting off the burner
For long periods only, (7 days or more) move electrical ON/OFF
switch to OFF, then turn gas control knob to OFF. Turn off gas
service cock. For shorter periods, leave heater under thermostat
control.
4.4.3 Checking main burner pressure
1. Turn gas control knob to OFF.
2. Release bleed screw A and connect pressure gauge tube.
3. Light burner as described previously.
4. Remove valve cap from port B and adjust pressure using
exposed screw in accordance with data plate.
5. Turn screw clockwise to increase pressure and
counterclockwise to decrease.
6. Turn gas control to PILOT. Remove pressure gauge tube
and tighten bleed screw A.
7. Turn gas control knob to ON and light burner as described
above.
See
If possible, check gas rate (see Technical Data) with
meter and watch. Refit valve cap to port B.
Fig. 28
Gas control
knob
A
B
Pink MV
Black PV-MV
Purple PV
Содержание 24/39
Страница 1: ......
Страница 65: ...Issue 2 14 07 16 65 Parts List and Illustrations 9 9 10 HIflo models 62 341 and 54 418 440 Natural Gas Fig 34 ...
Страница 69: ...Issue 2 14 07 16 69 Parts List and Illustrations 9 9 15 HIflo LPG models L62 309 L54 399 Fig 31 ...
Страница 112: ...112 Issue 2 14 07 16 ...
Страница 113: ...Issue 2 14 07 16 113 ...
Страница 114: ...114 Issue 2 14 07 16 ...