3.7 Air supply and ventilation
Note
The following notes are provided for general guidance
only.
Ventilation shall prevent the heater environment from
exceeding 32°C.
The purpose provided space in which the heater(s) are
installed must have permanent air vents communicating
directly with the outside air, at high and low level. Where
communication with the outside air is possible only by
means of high level air vents, ducting down to floor level
for the lower vents must be used.
For an exposed building, air vents must be fitted on at
least two sides, preferably on all four sides.
Air vents should have negligible resistance and must not
be sited in any position where they are likely to- be easily
blocked or flooded, or in any position adjacent to an
extraction system which is carrying flammable vapour.
Grilles or louvers should be so designed that high velocity
air streams do not occur within the space housing the
heater(s).
The grilles should have a total minimum free area for the
water heater(s) in addition to any other requirements as
follows:-
Where the heater is to be installed in a room the following
permanent ventilation is required:
5cm
2
per kW in excess of 7kW net for installations up to 54kW
net.
For installations exceeding 60kW the following permanent
ventilation is required:
Low Level (inlet) 540cm
2
plus 5cm
2
per kilowatt in excess of
54kW total net input.
High Level (outlet) 270cm
2
plus 2.5cm
2
per kilowatt in excess of
54kW total net input.
Where the heater is to be installed in a compartment, permanent
air vents are required in the compartment at high and low level.
These air vents must either communicate with a room or internal
space or be direct to outside air.
See
For all installations, please refer to the table below for
calculating requirements. Detailed recommendations for
the air supply are given in BS 5440 Part 2, BS 6644
Clause 19 and IGE/UP/10 Pt.1.
Содержание 24/39
Страница 1: ......
Страница 65: ...Issue 2 14 07 16 65 Parts List and Illustrations 9 9 10 HIflo models 62 341 and 54 418 440 Natural Gas Fig 34 ...
Страница 69: ...Issue 2 14 07 16 69 Parts List and Illustrations 9 9 15 HIflo LPG models L62 309 L54 399 Fig 31 ...
Страница 112: ...112 Issue 2 14 07 16 ...
Страница 113: ...Issue 2 14 07 16 113 ...
Страница 114: ...114 Issue 2 14 07 16 ...