Ax60+ Multi-Gas
Service Manual
Int. Approved
Document ref: P0159-803-11
September 2019
Page 58 of 62
Copyright © 2015 Analox Ltd. All Rights Reserved.
Commercial in Confidence
15
Appendix D
–
Default O
2
sensor configuration settings
The following table shows the configurable items that can be changed in the O
2
Sensor software menus.
Item
Default setting
Comment
Alarm One Enabled
FALSE
Enable alarm
Alarm One Set-point
19.50%
Threshold for the alarm
Alarm One Direction
Low Going
Can be set to either low going or high going
Alarm One Strobe Enable
FALSE
Activates the strobe on alarm
Alarm One Sounder Enable
FALSE
Activates the sounder on alarm
Alarm One Evacuation Enabled
FALSE
Activates the strobe and sounder of connected sensors on alarm
Alarm One Latching Enable
TRUE
Requires the user to mute and acknowledge the alarm before the alarm will clear
Alarm Two Enabled
TRUE
Enable alarm
Alarm Two Set-point
19.50%
Threshold for the alarm
Alarm Two Direction
Low Going
Can be set to either low going or high going
Alarm Two Strobe Enable
TRUE
Activates the strobe on alarm
Alarm Two Sounder Enable
FALSE
Activates the sounder on alarm
Alarm Two Evacuation Enabled
FALSE
Activates the strobe and sounder of connected sensors on alarm
Alarm Two Latching Enable
TRUE
Requires the user to mute and acknowledge the alarm before the alarm will clear
Alarm Three Enabled
TRUE
Enable alarm
Alarm Three Set-point
23.00%
Threshold for the alarm
Alarm Three Direction
High Going
Can be set to either low going or high going
Alarm Three Strobe Enable
TRUE
Activates the strobe on alarm
Alarm Three Sounder Enable
TRUE
Activates the sounder on alarm
Alarm Three Evacuation Enabled
FALSE
Activates the strobe and sounder of connected sensors on alarm
Alarm Three Latching Enable
TRUE
Requires the user to mute and acknowledge the alarm before the alarm will clear
Alarm Four Enabled
TRUE
Enable alarm
Alarm Four Set-point
18.00%
Threshold for the alarm
Alarm Four Direction
Low Going
Can be set to either low going or high going
Alarm Four Strobe Enable
TRUE
Activates the strobe on alarm
Alarm Four Sounder Enable
TRUE
Activates the sounder on alarm
Alarm Four Evacuation Enabled
FALSE
Activates the strobe and sounder of connected sensors on alarm
Alarm Four Latching Enable
TRUE
Requires the user to mute and acknowledge the alarm before the alarm will clear