54
•
MN-35947
•
Rev 15
•
01/18
•
Combitherm® CT PROformance™ and CT Classic Series Installation Manual
Installation
1-1/2" (40mm) diameter
CPVC Tee Fitting
Drain Connection
45 Degree Elbow
45 Degree Elbow
1-1/2" (40mm) diameter pipe
To Drain - Floor Sink
with Positive Descending Slope
Drain
Connection
1-1/2" (40mm) diameter
1-1/2" (40mm) CPVC
Tee Fitting Drain Connection
Exhaust vent opening
Drain materials must
withstand temperatures
up to 200°F (93°C).
If a drain run exceeds 6' (1829mm)
to the floor sink, an air gap is
strongly recommended.
When stacking ovens, run
independent drains.
Use only glue designed for CPVC.
Installation kits have a maximum run
length of 4-1/2' (1372mm).
Drain vent pipes must
be above oven exhaust
vent opening!
To prevent SERIOUS INJURY or PROPERTY DAMAGE
from slippery floor conditions, check drain is connected
properly and not blocked.
WARNING:
One suggested method of drain installation.
Local codes may require that the type of material used for the drain
pipes be different than the CPVC pipes provided in the installation kit.
In such cases, any costs associated with changing the drain pipes
to meet the local codes are the responsibility of the end user.
A union is required. Install a 1-1/2-inch (41mm) diameter connection, drain line and clamp into place. The drain
line must always be a positive gradient away from the Combitherm oven. An end of drain run air gap may be
required by local code. Vertical air vent required.
NOTICE:
In the U.S.A., this equipment is to be installed to comply with the Basic Plumbing Code of the Building
Officials and Code Administrators International, Inc. [BOCA], and the Food Service Sanitation Manual of
the Food & drug Administration [FdA].
WATER DRAINAgE – fOR STACKED OVEN