507961-01
Page 49 of 58
Issue 2128
96G2UH090CV12
Temp. Rise
Speed Adjustment
Heating CFM @ 0 - 0.8” w.c.
Setting D
Setting C
Setting B
Setting A
High Fire
60-90
+
1060
1135
1240
1430
Normal
960
1040
1120
1310
-
830
935
980
1175
Low Fire
35-65
+
960
1040
1120
1310
Normal
875
945
995
1195
-
790
840
920
1080
Cooling Stage
Cooling CFM @ 0 - 0.8” w.c.
2nd Stage
+
875
1040
1210
1360
Normal
800
945
1100
1245
-
720
840
970
1115
1st Stage
+
625
710
830
950
Normal
565
670
760
860
-
520
610
685
785
96G2UH090CV20
Temp. Rise
Speed Adjustment
Heating CFM @ 0 - 0.8” w.c.
Setting D
Setting C
Setting B
Setting A
High Fire
40-70
+
1450
1565
1725
1865
Normal
1310
1450
1585
1690
-
1155
1305
1450
1545
Low Fire
30-60
+
1120
1265
1420
1520
Normal
965
1120
1285
1395
-
865
950
1120
1235
Cooling Stage
Cooling CFM @ 0 - 0.8” w.c.
2nd Stage
+
1385
1595
1820
2020
Normal
1225
1465
1645
1885
-
1065
1320
1505
1675
1st Stage
+
935
1055
1275
1465
Normal
835
980
1120
1335
-
740
870
1010
1150