Combustion, Dilution & Ventilation Air

If this unit is installed as a Non-Direct Vent Furnace, follow 

the guidelines in this section.

NOTE: 

In Non-Direct Vent Installations, combustion air is 

taken from indoors and flue gases are discharged outdoors.

Insufficient  combustion  air  can  cause  headaches, 

nausea,  dizziness  or  asphyxiation.  It  will  also  cause 

excess water in the heat exchanger resulting in rusting 

and  premature  heat  exchanger  failure.  Excessive 

exposure  to  contaminated  combustion  air  will  result 

in  safety  and  performance  related  problems.  Avoid 

exposure to the following substances in the combustion 

air supply:

• 

Permanent wave solutions

• 

Chlorinated waxes and cleaners

• 

Chlorine base swimming pool chemicals

• 

Water softening chemicals

• 

De-icing salts or chemicals

• 

Carbon tetrachloride

• 

Halogen type refrigerants

• 

Cleaning solvents (such as perchloroethylene)

• 

Printing inks, paint removers, varnishes, etc.

• 

Hydrochloric acid

• 

Cements and glues

• 

Antistatic fabric softeners for clothes dryers

• 

Masonry acid washing materials

   WARNING

In the past, there was no problem in bringing in sufficient 

outdoor air for combustion. Infiltration provided all the air 

that  was  needed.  In  today’s  homes,  tight  construction 

practices  make  it  necessary  to  bring  in  air  from  outside 

for  combustion.  Take  into  account  that  exhaust  fans, 

appliance vents, chimneys, and fireplaces force additional 

air  that  could  be  used  for  combustion  out  of  the  house. 

Unless outside air is brought into the house for combustion, 

negative pressure (outside pressure is greater than inside 

pressure)  will  build  to  the  point  that  a  down  draft  can 

occur  in  the  furnace  vent  pipe  or  chimney.  As  a  result, 

combustion  gases  enter  the  living  space  creating  a 

potentially dangerous situation.

In the absence of local codes concerning air for combustion 

and ventilation, use the guidelines and procedures in this 

section to install these furnaces to ensure efficient and safe 

operation. You  must  consider  combustion  air  needs  and 

requirements for exhaust vents and gas piping. A portion 

of this information has been reprinted with permission from 

the National Fuel Gas Code (ANSI-Z223.1/NFPA 54). This 

reprinted material is not the complete and official position 

of ANSI on the referenced subject, which is represented 

only by the standard in its entirely.

In Canada, refer to the CSA B149 Installation codes.

Do not install the furnace in a corrosive or contaminated 

atmosphere.  Meet  all  combustion  and  ventilation  air 

requirements, as well as all local codes.

   CAUTION

All  gas-fired  appliances  require  air  for  the  combustion 

process.  If  sufficient  combustion  air  is  not  available, 

the  furnace  or  other  appliance  will  operate  inefficiently 

and  unsafely.  Enough  air  must  be  provided  to  meet  the 

needs of all fuel-burning appliances and appliances such 

as exhaust fans which force air out of the house. When 

fireplaces, exhaust fans, or clothes dryers are used at the 

same  time  as  the  furnace,  much  more  air  is  required  to 

ensure  proper  combustion  and  to  prevent  a  down  draft. 

Insufficient  air  causes  incomplete  combustion  which  can 

result in carbon monoxide.

In addition to providing combustion air, fresh outdoor air 

dilutes contaminants in the indoor air. These contaminants 

may  include  bleaches,  adhesives,  detergents,  solvents 

and  other  contaminants  which  can  corrode  furnace 

components.

The  requirements  for  providing  air  for  combustion  and 

ventilation  depend  largely  on  whether  the  furnace  is 

installed in an unconfined or a confined space.

Unconfined Space

An  unconfined  space  is  an  area  such  as  a  basement 

or  large  equipment  room  with  a  volume  greater  than  50 

cubic  feet  (1.42  m³)  per  1,000  Btu  (.29  kW)  per  hour  of 

the combined input rating of all appliances installed in that 

space. This space also includes adjacent rooms which are 

not separated by a door. Though an area may appear to 

be unconfined, it might be necessary to bring in outdoor air 

for combustion if the structure does not provide enough air 

by infiltration. If the furnace is located in a building of tight 

construction  with  weather  stripping  and  caulking  around 

the windows and doors, follow the procedures in the “Air 

from Outside” section.

Confined Space

A confined space is an area with a volume less than 50 

cubic  feet  (1.42  m³)  per  1,000  Btu  (.29  kW)  per  hour  of 

the combined input rating of all appliances installed in that 

space.  This  definition  includes  furnace  closets  or  small 

equipment rooms.

When the furnace is installed so that supply ducts carry 

air  circulated  by  the  furnace  to  areas  outside  the  space 

containing the furnace, the return air must be handled by 

ducts which are sealed to the furnace casing and which 

Содержание 96G2UH045BV12

Страница 1: ...ry or death Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a licensed professional installer or equivalent service agency or the gas supplier WARNING As with any mechanical equipment personal injury can result from contact with sharp sheet metal edges Be careful when you hand...

Страница 2: ...RAB Return Air Base 3 Bottom return air 4 Return air from both sides 5 Bottom and one side return air 2 Optional External Side Return Air Filter kit is not for use with optional Return Air Base Consider sizing requirements for optional IAQ equipment before cutting side return opening FRONT VIEW SIDE VIEW Unit Dimensions Model A B C D in mm in mm in mm in mm 045 12 070 12 17 1 2 448 16 3 8 416 16 4...

Страница 3: ...507961 01 Page 3 of 58 Issue 2128 Figure 1 Parts Arrangement ...

Страница 4: ... following 1 Snap bushing 1 Snap Plug 1 Wire tie 1 Condensate trap 1 Condensate trap cap 1 Condensate trap clamp 1 2 Diameter debris screen 1 3 4 Threaded street elbow Check equipment for shipping damage If you find any damage immediately contact the last carrier Please refer to specification sheets for available accessories Safety Information Improper installation adjustment alteration service or...

Страница 5: ... obtain a temperature rise within the range specified on the unit nameplate Failure to do so may cause erratic limit operation and premature heat exchanger failure This furnace must be installed so that its electrical components are protected from water Installed in Combination with a Cooling Coil When this furnace is used with cooling units Figure 4 it shall be installed in parallel with or on th...

Страница 6: ...ILURE TO FOLLOW THE ABOVE INSTALLATION INSTRUCTIONS FAILURE TO FOLLOW THE ABOVE INSTALLATION INSTRUCTIONS VOIDS THE MANUFACTURER S EQUIPMENT LIMITED WARRANTY ALLIED AIR DISCLAIMS ALL LIABILITY IN CONNECTION WITH INSTALLER S FAILURE TO FOLLOW THE ABOVE INSTALLATION INSTRUCTIONS General These instructions are intended as a general guide and do not supersede local codes in any way Consult authorities...

Страница 7: ... position of ANSI on the referenced subject which is represented only by the standard in its entirely In Canada refer to the CSA B149 Installation codes Do not install the furnace in a corrosive or contaminated atmosphere Meet all combustion and ventilation air requirements as well as all local codes CAUTION All gas fired appliances require air for the combustion process If sufficient combustion a...

Страница 8: ...ng shall be within 12 305 mm of the top of the enclosure and one within 12 305 mm of the bottom These openings must communicate directly or by ducts with the outdoors or spaces crawl or attic that freely communicate with the outdoors or indirectly through vertical ducts Each opening shall have a minimum free area of 1 square inch per 4 000 Btu 645 mm per 59 kW per hour of the total input rating of...

Страница 9: ...tal louvers and grilles will have 60 to 75 percent free area Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation Figure 10 Equipment in Confined Space Inlet Air from Ventilated Crawlspace and Outlet Air to Outside Roof Terminated Exhaust Pipe Furnace Ventilation Louvers Crawl Space Intake Debris S...

Страница 10: ...ections and installation and service clearances 24 inches 610 mm at unit front The unit must be level from side to side Tilt the unit slightly maximum 1 2 in from level from back to front to aid in the draining of the heat exchanger See Figure 13 Allow for clearances to combustible materials as indicated on the unit nameplate Figure 12 Installation Clearances Top Right Side Left Side Bottom floor ...

Страница 11: ... The furnace is equipped with a removable bottom panel to facilitate installation Markings are provided on both sides of the furnace cabinet for installations that require side return air Cut the furnace cabinet at the maximum dimensions shown on Page 2 Furnace applications which include side return air and a condensate trap installed on the same side of the cabinet trap can be installed remotely ...

Страница 12: ...and air discharge Refer to Figure 18 for clearances in horizontal applications Figure 18 Horizontal Application Installation Clearances Top Bottom floor Air Flow Air Flow Right Hand Discharge Left Hand Discharge Bottom floor Top Right End Left End Air Flow Air Flow Right End Left End Top 0 Front 0 Back 0 Ends 0 Vent 0 Floor 0 Front clearance in alcove installation must be 24 in 610 mm Maintain a m...

Страница 13: ...If unit is installed above finished space fabricate an auxiliary drain pan to be installed under unit Set unit in drain pan as shown in Figure 20 Leave 8 inches for service clearance below unit for condensate trap 3 Provide a service platform in front of unit When installing the unit in a crawl space a proper support platform may be created using cement blocks 4 Route auxiliary drain line so that ...

Страница 14: ...equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal If a filter is installed size the return air duct to fit the filter frame Pipe Fittings Specifications All pipe fittings primer and solvent cement must conform withAmerican National Standard Institute and theAmerican Society for Testing and Materials ANSI ASTM standards The solvent shall be free flowing and...

Страница 15: ...inutes before placing unit into operation DANGER 1 Measure and cut vent pipe to desired length 2 Debur and chamfer end of pipe removing any ridges or rough edges If end is not chamfered edge of pipe may remove cement from fitting socket and result in a leaking joint 3 Clean and dry surfaces to be joined 4 Test fit joint and mark depth of fitting on outside of pipe 5 Uniformly apply a liberal coat ...

Страница 16: ...he venting system being placed into operation while all other appliances connected to the venting system are not in operation WARNING Capacity VENT PIPE DIA in STANDARD CONCENTRIC Outdoor Exhaust Accelerator Dia X Length Outdoor Exhaust Accelerator Dia X Length Flush Mount Kit 1 1 2 Concentric Kit 2 Concentric Kit 3 Concentric Kit 1 1 2 X 12 2 X 12 51W11 71M80 or 44W92 69M29 or 44W92 60L46 or 44W9...

Страница 17: ... is probably oversized for the single water heater or other appliance The vent should be checked for proper draw with the remaining appliance Exhaust Piping Route piping to outside of structure Continue with installation following instructions given in piping termination section Do Not discharge exhaust into an existing stack or stack that also serves another gas appliance If vertical discharge th...

Страница 18: ...tal in exhaust or intake terminations Doing so will cause freeze ups and may block the terminations IMPORTANT Table 4 Minimum Vent Pipe Lengths Capacity Min Vent Length 045 070 090 110 135 15 ft or 5 ft plus 2 elbows or 10 ft plus 1 elbow Any approved termination may be added to the minimum length listed Use the following steps to correctly size vent pipe diameter 045 070 090 110 135 btuh Standard...

Страница 19: ...36 21 70 70 48 13 93 92 73 73 69 10 31 16 65 65 43 8 88 87 68 68 64 Standard Termination Elevation 4 501 10 000 ft Number of 90 Elbows Used 1 1 2 Pipe 2 Pipe 2 1 2 Pipe 3 Pipe Capacity Capacity Capacity Capacity 45 70 90 110 135 45 70 90 110 135 45 70 90 110 135 45 70 90 110 135 1 25 20 n a n a n a 76 61 39 n a n a 110 110 88 53 n a 133 132 113 113 109 2 20 15 71 56 34 105 105 83 48 128 127 108 10...

Страница 20: ...28 13 60 60 44 9 76 76 69 69 60 10 23 8 55 55 39 n a 71 71 64 64 55 Concentric Termination Elevation 4 501 10 000 ft Number of 90 Elbows Used 1 1 2 Pipe 2 Pipe 2 1 2 Pipe 3 Pipe Capacity Capacity Capacity Capacity 45 70 90 110 135 45 70 90 110 135 45 70 90 110 135 45 70 90 110 135 1 25 20 n a n a n a 68 53 37 n a n a 100 100 84 49 n a 116 116 109 109 100 2 20 15 63 48 32 95 95 79 44 111 111 104 10...

Страница 21: ...3 53 49 10 21 6 50 50 28 68 67 48 48 44 Standard Termination at Elevation 4 501 10 000 ft Number of 90 Elbows Used 1 1 2 Pipe 2 Pipe 2 1 2 Pipe 3 Pipe Capacity Capacity Capacity Capacity 45 70 90 110 135 45 70 90 110 135 45 70 90 110 135 45 70 90 110 135 1 25 20 n a n a n a 66 51 29 n a n a 95 95 73 38 n a 113 112 93 93 89 2 20 15 61 46 24 90 90 68 33 108 107 88 88 84 3 15 10 56 41 19 85 85 63 28 ...

Страница 22: ...t Applications TYPICAL EXHAUST PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON DIRECT VENT APPLICATIONS RIGHT HAND DISCHARGE SHOWN SIDE VIEW 45 MAX 45 MAX 2 2 2 2 or 2 12 max EXHAUST TRANSITION 3 2 2 EXHAUST TRANSITION 1 1 2 2 2 EXHAUST or NOTE 1 1 2 Vent Pipe Diameter Allowed Only on 045 070 Units DO NOT transition from larger to smaller pipe in horizontal runs of exhaust pipe EXHAUST DO NOT transit...

Страница 23: ...d Discharge Shown Intake Piping Figure 27 through Figure 30 This gas furnace may be installed in either direct vent or non direct vent applications In non direct vent applications when intake air will be drawn into the furnace from the surrounding space the indoor air quality must be considered and guidelines listed in Combustion Dilution and Ventilation Air section must be followed Follow the nex...

Страница 24: ...form Ensure that the intake air inlet will not be obstructed by loose insulation or other items that may clog the debris screen 2 If intake air is drawn from a ventilated attic Figure 31 or ventilated crawlspace Figure 32 the exhaust vent length must not exceed those listed in Table 5C If 3 diameter pipe is used reduce to 2 diameter pipe at the termination point to accommodate the debris screen 3 ...

Страница 25: ...ons and 12 above the average snow accumulation At vent termination care must be taken to maintain protective coatings over building materials prolonged exposure to exhaust condensate can destroy protective coatings It is recommended that the exhaust outlet not be located within 6 feet 1 8 m of a condensing unit because the condensate can damage the painted coating NOTE See Table 6 for maximum allo...

Страница 26: ... N A 3 in N A N A N A N A 8 8 7 7 13 13 1 Refer to 99 Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook 2 Poly Propylene vent pipe PP by Duravent and Centrotherm 3 Vent length in table is equivalent length Each elbow is equivalent to 5ft of straight pipe and should be included when measuring total length NOTE Concentric terminations are the equiva...

Страница 27: ...er veranda porch deck or balcony 12 Equal to or greater than soffit depth 3 feet 9m 12 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3 feet 9m 6 inches 152mm for appliances 10 000 Btuh 3kw 12 inches 305mm for appliances 10 000 Btuh 3kw and 100 000 Btuh 30kw 36 inches 9m for appliances 100 000 Btuh 30kw 3 feet 9m above if within 10 feet 3m horizontally 6 feet 1 8m 7 feet...

Страница 28: ...r appliances 10 000 pliances 10 000 Btuh 3kw and 50 000 pliances 50 000 Btuh 15kw 6 inches 152mm for appliances 10 000 Btuh 3kw 12 inches 305mm for appliances 10 000 Btuh 3kw and 100 000 Btuh 30kw 36 inches 9m for appliances 100 000 Btuh 30kw 3 feet 9m above if within 10 feet 3m horizontally 6 feet 1 8m 7 feet 2 1m 12 inches 305mm 1 In accordance with the current ANSI Z223 1 NFPA 54 Natural Fuel G...

Страница 29: ...ng should terminate straight down using two 90 elbows see Figure 36 4 Exhaust piping must terminate straight out or up as shown A reducer may be required on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake piping See Table 7 Figure 36 Direct Vent Roof Termination Kit 15F75 or 44J41 UNCONDITIONED ATTIC SPACE SIZE PER EXHAUST PIPE T...

Страница 30: ... 41 Direct Vent Concentric Wall Termination 71M80 69M29 OR 60L46 US 41W92 or 41W93 Canada 12 305mm Min above grade or average snow accumulation INTAKE AIR INTAKE AIR INTAKE AIR OUTSIDE WALL GRADE CLAMP Not Furnished FIELD PROVIDED REDUCER MAY BE REQUIRED TO ADAPT DIFFERENT VENT PIPE SIZE TO TERMINATION EXHAUST VENT 1 1 2 38mm accelerator provided on 71M80 44W92 kits for 045 and 070 models EXHAUST ...

Страница 31: ... grade or average snow accumulation B Horizontal separation between intake and exhaust C Minimum from end of exhaust to inlet of intake D Exhaust pipe length E Wall support distance from top of each pipe intake exhaust 12 305 mm Min 12 305 mm Min 6 152 mm Min 24 610 mm Max 9 227 mm Min 12 305 mm Min 16 405 mm Max 6 152 mm Max 6 152 mm Min 24 610 mm Max 9 227 mm Min 12 305 mm Min 20 508 mm Max 6 15...

Страница 32: ... ACCUMULATION SIZE PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE Figure 46 Non Direct Vent Field Supplied Wall Termination SIZE TERMINATION PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE FIELD PROVIDED REDUCER MAY BE REQUIRED TO ADAPT DIFFERENT VENT PIPE SIZE TO TERMINATION SIZE TERMINATION PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE Use wall support every 24 610 mm Use two supports o...

Страница 33: ...Termination Drain Trap assembled Figure 49 Kit 51W18 USA 15Z70 Canada Parts Identification and Assembly Exhaust from Furnace To Termination Exhaust from Furnace To Termination Kit 51W18 is shown Figure 50 Crawl Space Vent Pipe Drain Trap Assembled Incorrectly Figure 51 Upflow or Downflow Furnace with Exhaust through Crawl Space KIT 51W18 USA Basement Floor To Termination 1 2 PVC to Code Approved D...

Страница 34: ...om the furnace to the drain Do not use copper tubing or existing copper condensate lines for drain line CAUTION 5 Figure 54 and Figure 55 show the furnace and evaporator coil using a separate drain If necessary the condensate line from the furnace and evaporator coil can drain together See Figure 56 and Figure 57 Upflow furnace Figure 53 In upflow furnace applications the field provided vent must ...

Страница 35: ...ion using a separate drain Piping from furnace must slope down a minimum of 1 4 per ft toward trap Figure 55 Unit with Evaporator Coil Using a Separate Drain Figure 56 Evaporator Coil Using a Common Drain Figure 57 Evaporator Coil Using a Common Drain Piping from furnace must slope down a minimum of 1 4 per ft toward trap ...

Страница 36: ...507961 01 Page 36 of 58 Issue 2128 Figure 58 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...

Страница 37: ...r gas vents dumb waiters or elevator shafts Center gas line through piping hole Gas line should not touch side of unit See Figure 61 and Figure 62 4 Piping should be sloped 1 4 per 15 feet 6 mm per 5 6 m upward toward the gas meter from the furnace The piping must be supported at proper intervals every 8 to 10 feet 2 44 to 3 05 m using suitable hangers or straps Install a drip leg in vertical pipe...

Страница 38: ...pflow Applications Possible Gas Piping Configurations Figure 62 Horizontal Applications Possible Gas Piping Configurations NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET FIELD PROVIDED AND INSTALLED GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE Horizontal Application Right Side Air Discharge Gas Valve GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE GROUND JOINT UNION DRIP...

Страница 39: ... 16 42 530 15 01 490 13 87 460 13 03 430 12 18 400 11 33 1 1 2 38 1 1 610 40 894 2100 59 46 460 41 34 1180 33 41 990 28 03 900 25 48 810 22 94 750 21 24 690 19 54 650 18 41 620 17 56 2 50 8 2 067 52 502 3950 111 85 2750 77 87 2200 62 30 1900 53 80 1680 47 57 1520 43 04 1400 39 64 1300 36 81 1220 34 55 1150 32 56 2 1 2 63 5 2 469 67 713 6300 178 39 4350 123 17 3520 99 67 3000 84 95 2650 75 04 2400 ...

Страница 40: ...near the furnace so that power can be turned off for servicing Table 9 Capacity Maximum Over Current Protection Amps 045B12 070B12 090C12 15 090C16 090C20 110C16 110C20 135D20 20 4 Before connecting the thermostat check to make sure the wires will be long enough for servicing at a later date Make sure that thermostat wire is long enough to facilitate future removal of blower for service 5 Complete...

Страница 41: ...hermostat the wiring to be done and any replacement of wire shall conform with the temperature limitation for Type T wire 63 F 35 C rise Connect a sufficiently sized wire with ground to the furnace s line voltage connections and ground wire Refer to the furnace rating plate for electrical characteristics to be used in sizing field supply wiring and overcurrent protection The line voltage supply sh...

Страница 42: ...fication Both the passive and active dehumidification methods described above can be utilized on the same furnace Circulating Airflow Adjustments Cooling Mode The units are factory set for the highest airflow for each model Adjustments can be made to the cooling airflow by repositioning the jumper plug marked COOL A B C D see Figure 66 To determine what CFM the motor is delivering at any time coun...

Страница 43: ... blower remains energized until the limits are closed Fan On When the thermostat is set for continuous fan operation and there is no demand for heating or cooling a call for fan closes the R to G circuit and the circulating blower motor runs at 38 of the selected cooling CFM until switched off When the call for fan is turned off the control de energizes the circulating blower Cooling The unit is s...

Страница 44: ...e W1 W2 Heat Call Figure 68 Indoor Blower Operation High Heat W2 Call Figure 69 Indoor Blower Operation Call for Fan Percentage of High Stage Cooling Figure 70 Indoor Blower Operation Single Stage Cooling Figure 71 Indoor Blower Operation Two Stage Cooling Percentage of High Stage Cooling ...

Страница 45: ...own by a red LED on the control board The control continuously monitors its own operation and the operation of the system If a failure occurs the LED will indicate the failure code The flash codes are presented in Table 10 Fault Code History Button The control stores the last five fault codes in memory A push button switch is located on the control When the push button switch is pressed and releas...

Страница 46: ...AUSE INJURY OR DEATH UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES NOTE IF ANY WIRE IN THIS APPLIANCE IS REPLACED IT MUST BE REPLACED WITH WIRE OF LIKE SIZE RATING INSULATION THICKNESS AND TERMINATION FIELD SUPPLIED ACC WIRE S145 IS USED WITH HONEYWELL GAS VALVE WHEN APPLIED IN LP GAS UNITS ...

Страница 47: ...NG MATERIAL HAVING A TEMP RATING OF AT LEAST 90 c 3 PROPER POLARITY MUST BE OBSERVED FOR FIELD LINE VOLTAGE SUPPLY IGNITION CONTROL WILL LOCK OUT IF POLARITY IS REVERSED 4 FOR TEMPORARY SERVICE REPLACEMENT OF CIRCULATING BLOWER MOTOR WITH PSC MOTOR CONNECT DESIRED SPEED TAP TO EAC TERMINAL AND NEUTRAL TAP TO NEUTRAL TERMINAL ON IGNITION CONTROL 5 DO NOT CONNECT C COMMON CONNECTION BETWEEN INDOOR U...

Страница 48: ...075 1210 1370 Normal 815 980 1120 1255 720 885 1020 1135 1st Stage 595 760 865 980 Normal 540 660 785 890 485 600 695 790 96G2UH070BV12 Temp Rise Speed Adjustment Heating CFM 0 0 8 w c Setting D Setting C Setting B Setting A High Fire 50 80 965 1130 1255 1400 Normal 880 990 1140 1295 810 890 1030 1170 Low Fire 25 55 940 1070 1195 1345 Normal 830 965 1100 1235 755 840 975 1130 Cooling Stage Cooling...

Страница 49: ... Normal 800 945 1100 1245 720 840 970 1115 1st Stage 625 710 830 950 Normal 565 670 760 860 520 610 685 785 96G2UH090CV20 Temp Rise Speed Adjustment Heating CFM 0 0 8 w c Setting D Setting C Setting B Setting A High Fire 40 70 1450 1565 1725 1865 Normal 1310 1450 1585 1690 1155 1305 1450 1545 Low Fire 30 60 1120 1265 1420 1520 Normal 965 1120 1285 1395 865 950 1120 1235 Cooling Stage Cooling CFM 0...

Страница 50: ...rmal 1220 1405 1570 1795 1075 1270 1430 1635 1st Stage 935 1065 1245 1405 Normal 865 970 1145 1280 790 890 1025 1165 96G2UH135DV20 Temp Rise Speed Adjustment Heating CFM 0 0 8 w c Setting D Setting C Setting B Setting A High Fire 55 85 1650 1845 2000 2195 Normal 1495 1660 1880 1985 1360 1500 1670 1850 Low Fire 40 70 1300 1435 1630 1715 Normal 1190 1325 1465 1620 1095 1190 1340 1430 Cooling Stage C...

Страница 51: ... Allowed Allowed Allowed Allowed Norm Allowed Allowed Factory Setting Allowed 10 Allowed Allowed Allowed Allowed 96G2UH090CV20 10 Allowed Allowed Allowed Allowed Norm Allowed Allowed Factory Setting Allowed 10 Allowed Allowed Allowed Allowed 96G2UH110CV20 10 Allowed Allowed Allowed Allowed Norm Allowed Allowed Factory Setting Allowed 10 Allowed Allowed Allowed Allowed 96G2UH135DV20 10 Allowed Allo...

Страница 52: ...ight burners on this furnace Each time the thermostat calls for heat the burners will automatically light The ignitor does not get hot when there is no call for heat on these units Gas Valve Operation 1 STOP Read the safety information at the beginning of this section Figure 74 2 Set the thermostat to the lowest setting 3 Turn OFF all electrical power to the unit 4 This furnace is equipped with an...

Страница 53: ...ent Gas Flow Approximate Capacity Seconds for One Revolution Natural LP 1 cu ft Dial 2 cu ft Dial 1 cu ft Dial 2 cu ft Dial 045 80 160 200 400 70 55 110 136 272 90 41 82 102 204 110 33 66 82 164 135 27 54 68 136 Natural 1000 btu cu ft LP 2500 btu cu ft Table 15 Gas Meter Clocking Chart Furnace should operate at least 5 minutes before checking gas flow Determine time in seconds for two revolutions ...

Страница 54: ...reset switches are located on the front of the burner box Pressure Switch The pressure switch is located in the heating compartment on the cold end header box This switch checks for proper combustion air inducer operation before allowing ignition trial The switch is factory set and must not be adjusted Temperature Rise After the furnace has been started and supply and return air temperatures have ...

Страница 55: ...f power to the furnace 2 Have a shallow pan ready to empty condensate water 3 Remove the clean out cap from the condensate trap and empty water Inspect the trap then reinstall the clean out cap Cleaning Heat Exchanger If cleaning the heat exchanger becomes necessary follow the below procedures and refer to Figure 1 when disassembling unit Use papers or protective covering in front of furnace while...

Страница 56: ...on box 37 Reinstall the combustion air inducer and flexible no hub connector Reconnect the 2 pin plug to the wire harness 38 Reconnect drain tubes between flue collar and cold end header box 39 Secure burner assembly to vestibule panel using four existing screws Burners are self aligning to center of clam shells 40 Reconnect gas supply line to gas valve 41 Reconnect flame rollout switch wires 42 R...

Страница 57: ...ions Problems detected during the inspection may make it necessary to temporarily shut down the furnace until the items can be repaired or replaced Instruct the homeowners to pay attention to their furnace Situations can arise between annual furnace inspections that may result in unsafe operation For instance items innocently stored next to the furnace may obstruct the combustion air supply This c...

Страница 58: ...m height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not app...

Отзывы: