Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
99
Chapter 5 Configure the Configurable Flowmeter Module
C.OutputSetup[0].TieToCounter
Ties a channel to output 0
0 = No connection
1 = Connect Channel0 to Output0
2 = Connect Channel1 to Ouput0
0
C.Operations[0].OperationalMode
Decimal
SINT
Sets the module’s operational mode.
0 = OFF
1 = Totalizer Mode
2 = Non-Resettable Totalizer Mode
3 = High Resolution Frequency Mode
1
C.Ch0LowFreqClear
Decimal
BOOL
Enables the minimum detectable frequency level for
Channel 0.
Set the bit to 1 to enable it
1
C.Ch0PreTrigger
Decimal
BOOL
Enables the PreTrigger on Channel 0 for full flow.
Set the bit to 1 to enable it
1
C.Operations[0].FillMode
Decimal
SINT
Sets the Trickle mode to complete on fill total target or
time.
0 = Fill total target (Engineering units)
1 = Time (seconds)
0
O.OutputControl[0].0
Decimal
BOOL
Manually sets the operation of outputs connected to
channel 0.
0 = Module operation of outputs
1 = Override Output0 to 0
2 = Override Output0 to 1
0
O.Total[0].FillEnable
Decimal
BOOL
Enables the filling operation on output connected to
channel 0.
0 = Fill operation is disabled
1 = Fill operation is enabled.
0
O.Total[0].FillStart
Decimal
BOOL
Begins filling operation when Fill Enable is enabled on
output connected to channel 0.
0 = Do not begin filling
1 = Begin filling
0
O.Total[0].FillHold
Decimal
BOOL
Holds/pauses filling operation on output connected to
channel 0
0 = Continue filling operation
1 = Hold/pause filling operation
0
O.Total[0].FillTotalTarget
Float
REAL
Target for Fill Complete, except when Fill Transition is
greater than this value.
100
O.Total[0].FillTransition
Float
REAL
When fill cycle is started, trickle flow is initiated when the
Fill Total is equal to or greater than this value. Full flow is
initiated when the Fill Total is less than this value.
75
O.Total[0].FillTransitionTimer
Float
REAL
When timed trickle flow is selected, the status remains ON
for this time during this state.
The value must be changed prior to entering the trickle
flow state.
1.0
O.Total[0].Overrange
Decimal
BOOL
Enables the Overrange alarm on output connected to
channel 0. When the Frequency Period exceeds 100KHz,
this alarm is set.
0 = No Alarm
1 = Alarm Enabled
0
O.Total[0].Overflow
Decimal
BOOL
Enables the Overflow alarm on output connected to
channel 0. When the Total Counts exceeds the Roll Over
value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
0
O.Total[0].Overspeed
Decimal
BOOL
Enables the Overspeed alarm on output connected to
channel 0. When the Speed exceeds the Highest Allowed
Frequency value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
1
Table 9 - Tag Changes Required for Totalizer Mode Using Filler Function
Name
Style
Data Type
Definition
Enter This
Value
Содержание 1756-CFM
Страница 1: ...ControlLogix Configurable Flowmeter Module Catalog Number 1756 CFM User Manual Original Instructions...
Страница 8: ...8 Rockwell Automation Publication 1756 UM010C EN P June 2021 Notes...
Страница 118: ...118 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix B Software Configuration Tags Notes...
Страница 124: ...124 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix C Module Schematics Notes...
Страница 149: ...Rockwell Automation Publication 1756 UM010C EN P June 2021 149 ControlLogix Configurable Flowmeter Module User Manual...