Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
101
Chapter 5 Configure the Configurable Flowmeter Module
Digital Filter
You can use the C.Operations[0].FilterControl and
C.Operations[1].FilterControl tags to digitally configure the filters. The filter
applies to only F0/Z0 or F1/Z1 depending on which config byte they are
referencing.
Table 10 - Digital Filter Configuration
C.Operations[0].FilterControl affects F0/Z0
C.Operations[1].FilterControl affects F1/Z1
Byte
50 Hz filter for F
0x01
50 Hz filter for Z
0x02
50 Hz filter for F and Z
0x03
1 s debounce filter for Z
0x04
50 Hz filter for Z, 1 s debounce filter for Z
0x06
50 Hz filter for F, Z, and 1 s debounce filter for Z
0x07
500 Hz filter for F
0x08
5 kHz filter for F
0x09
50 kHz filter for F
0x0A
500 Hz filter for Z
0x0B
5 kHz filter for Z
0x0C
50 kHz filter for Z
0x0D
500 Hz filter for F and Z
0x0E
5 kHz filter for F and Z
0x0F
50 kHz filter for F and Z
0x10
50 Hz filter for F and 500 Hz filter for Z
0x11
50 Hz filter for F and 5 kHz filter for Z
0x12
50 Hz filter for F and 50 kHz filter for Z
0x13
500 Hz filter for F and 50 Hz filter for Z
0x14
500 Hz filter for F and 5 kHz filter for Z
0x15
500 Hz filter for F and 50 kHz filter for Z
0x16
5 kHz filter for F and 50 Hz filter for Z
0x17
5 kHz filter for F and 500 Hz filter for Z
0x18
5 kHz filter for F and 50 kHz filter for Z
0x19
50 kHz filter for F and 50 Hz filter for Z
0x1A
50 kHz filter for F and 500 Hz filter for Z
0x1B
50 kHz filter for F and 5 kHz filter for Z
0x1C
500 Hz filter for F, Z, and 1 s debounce filter for Z
0x1D
5 kHz filter for F, Z, and 1 s debounce filter for Z
0x1E
50 kHz filter for F, Z, and 1 s debounce filter for Z
0x1F
500 Hz filter for Z and 1 s debounce filter for Z
0x20
5 kHz filter for Z and 1 s debounce filter for Z
0x21
50 kHz filter for Z and 1 s debounce filter for Z
0x22
50 Hz filter for F, 500 Hz filter for Z and 1 s debounce filter for Z
0x23
50 Hz filter for F, 5 kHz filter for Z and 1 s debounce filter for Z
0x24
50 Hz filter for F, 50 kHz filter for Z and 1 s debounce filter for Z
0x25
500 Hz filter for F, 50 Hz filter for Z and 1 s debounce filter for Z
0x26
Содержание 1756-CFM
Страница 1: ...ControlLogix Configurable Flowmeter Module Catalog Number 1756 CFM User Manual Original Instructions...
Страница 8: ...8 Rockwell Automation Publication 1756 UM010C EN P June 2021 Notes...
Страница 118: ...118 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix B Software Configuration Tags Notes...
Страница 124: ...124 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix C Module Schematics Notes...
Страница 149: ...Rockwell Automation Publication 1756 UM010C EN P June 2021 149 ControlLogix Configurable Flowmeter Module User Manual...