Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
123
Appendix C Module Schematics
Series B Module
The 1756-CFM/B module contains two output circuits. Customer supplied
power, ranging from +5V DC…+31.2V DC, is connected internally through
terminals #18 and 20 to the power output transistors, for example, Q28 as
depicted above.
When an output is turned on, current flows into the source, out of the drain,
through the load connected to the ground of the customer supply (customer
return). Diode D34 protects the power output transistor Q11 from damage due
to inductive loads.
Output transistor Q28 is thermally protected by MOS Driver and turns off at
approximately 1.2 A. After an output goes into thermal shutdown, you must fix
the cause of the shutdown and toggle the output OFF and ON to re-energize
the output.
IMPORTANT
This schematic represents the Series B module
R59
R51
VCC
Isolation
R232
D30
Customer Common
R202
D42
R211
Customer Common
C186
R201
D34
C192
R222
Q28
D38
Customer Common
Customer Common
Customer Common
F1
Output 0
Customer VCC
16
18
Other Output channel
MOS Driver
Содержание 1756-CFM
Страница 1: ...ControlLogix Configurable Flowmeter Module Catalog Number 1756 CFM User Manual Original Instructions...
Страница 8: ...8 Rockwell Automation Publication 1756 UM010C EN P June 2021 Notes...
Страница 118: ...118 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix B Software Configuration Tags Notes...
Страница 124: ...124 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix C Module Schematics Notes...
Страница 149: ...Rockwell Automation Publication 1756 UM010C EN P June 2021 149 ControlLogix Configurable Flowmeter Module User Manual...