Chapter 3 Configurable Flowmeter Module Features and Operational Modes
Operating in Totalizer Mode
In Totalizer mode, the 1756-CFM module counts pulses and scales them to
engineering units. Every effort is made to store the least significant count even
when the least significant unit of the total is larger. The module calculates
three forms of calculated frequency:
•
Frequency over a fixed period
•
Frequency over a requested number of samples
•
Moving average of the frequency
All of the forms mentioned above are available in Totalizer mode. In this mode,
the module also offers these functions:
•
Prover function
•
Filler function
These functions are described later in this chapter.
Nonresettable Totalizer
Configure the module for Nonresettable Totalizer mode to make sure the total
counts value is not reset during normal module operation. The module stores
total count values up to 2
31
-1 (2,147,483,647) counts.
Terminal Usage in Totalizer Mode
In Totalizer mode, F0 and F1 are used as inputs. Z0 and Z1 are used as prover
signals.
Output Operation in Totalizer Mode
In Totalizer mode, outputs:
•
can operate normally or be forced ON or OFF.
•
can be tied to either flowmeter input. If one channel is configured for
trickle operation, both outputs are tied to that flowmeter input.
IMPORTANT
The total count value can be reset in Nonresettable Totalizer mode if
power is cycled to the module for any reason (for example, module is
removed from and reinserted to the chassis).
Содержание 1756-CFM
Страница 1: ...ControlLogix Configurable Flowmeter Module Catalog Number 1756 CFM User Manual Original Instructions...
Страница 8: ...8 Rockwell Automation Publication 1756 UM010C EN P June 2021 Notes...
Страница 118: ...118 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix B Software Configuration Tags Notes...
Страница 124: ...124 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix C Module Schematics Notes...
Страница 149: ...Rockwell Automation Publication 1756 UM010C EN P June 2021 149 ControlLogix Configurable Flowmeter Module User Manual...