94
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
Chapter 5 Configure the Configurable Flowmeter Module
C.OutputSetup[0].TieToCounter
Ties a channel to output 0
0 = No connection
1 = Connect Channel0 to Output0
2 = Connect Channel1 to Ouput0
0
C.Ch0ProverDirection
Decimal
BOOL
Defines the direction of a prover connected to Channel 0.
0 = unidirectional prover
1 = bidirectional prover
0
C.Ch0LowFreqClear
Decimal
BOOL
Enables the minimum detectable frequency level for
Channel 0.
Set the bit to 1 to enable it
1
C.Operations[0].OperationalMode
Decimal
SINT
Sets the module’s operational mode.
0 = OFF
1 = Totalizer Mode
2 = Non-Resettable Totalizer Mode
3 = High Resolution Frequency Mode
2
O.OutputControl[0].0
Decimal
BOOL
Manually sets the operation of outputs connected to
channel 0.
0 = Module operation of outputs
1 = Override Output0 to 0
2 = Override Output0 to 1
0
O.Total[0].ProverEnable
Decimal
BOOL
Enables the prover operation on output connected to
channel 0. Once this bit is enabled, the module waits for
output Z
0
to energize before beginning prover operations.
0 = Prover operation is disabled
1 = Prover operation is enabled
0
O.Total[0].Overrange
Decimal
BOOL
Enables the Overrange alarm on output connected to
channel 0. When the Frequency Period exceeds 100KHz,
this alarm is set.
0 = No Alarm
1 = Alarm Enabled
0
O.Total[0].Overflow
Decimal
BOOL
Enables the Overflow alarm on output connected to
channel 0. When the Total Counts exceeds the Roll Over
value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
0
O.Total[0].Overspeed
Decimal
BOOL
Enables the Overspeed alarm on output connected to
channel 0. When the Speed exceeds the Highest Allowed
Frequency value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
1
O.Total[0].Acceleration
Decimal
BOOL
Enables the Acceleration alarm on output connected to
channel 0. When the absolute acceleration exceeds the
Acceleration Alarm value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
1
I.Status[0].ProverState
Decimal
SINT
Displays status of the prover operation on channel 0
0 = Prover Not Active
1 = Prover waiting for 1
st
start
2 = Prover waiting for 1
st
stop
3 = Prover waiting for 2
nd
start
4 = Prover waiting for 2
nd
stop
5 = Prover Complete
I.Status[0].TotalCounts
Decimal
DINT
Displays actual pulses counted by the counter connected
to the channel 0
I.Status[0].FreqAverage
Float
REAL
Displays frequency averaged over the Meter samples on
channel 0
I.Status[0].FreqPeriod
Float
REAL
Displays frequency using sample time on channel 0
I.Status[0].Speed
Float
REAL
Displays frequency using filter resolution on channel 0
Table 8 - Tag Changes Required for Totalizer Mode Using Prover Function
Name
Style
Data Type
Definition
Enter This
Value
Содержание 1756-CFM
Страница 1: ...ControlLogix Configurable Flowmeter Module Catalog Number 1756 CFM User Manual Original Instructions...
Страница 8: ...8 Rockwell Automation Publication 1756 UM010C EN P June 2021 Notes...
Страница 118: ...118 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix B Software Configuration Tags Notes...
Страница 124: ...124 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix C Module Schematics Notes...
Страница 149: ...Rockwell Automation Publication 1756 UM010C EN P June 2021 149 ControlLogix Configurable Flowmeter Module User Manual...