Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
91
Chapter 5 Configure the Configurable Flowmeter Module
Sample Configuration for
Totalizer Mode
Prover Function
In the Totalizer mode prover function, the 1756-CFM module interfaces to a
prover and counts pulses using a Flowmeter or positive displacement meter.
The module then scales pulse count to engineering units. The module also
calculates frequency over a user-defined time period.
When using Totalizer mode (with prover or fill function), you can apply a K-
factor as a function of frequency, as shown.
This section offers a sample configuration to configure your module for
Totalizer mode prover function. In this configuration, channel 0 is configured
and channel 1 is left unused. For a detailed explanation of the features available
in this mode, see
Follow these steps to configure your module for Totalizer mode
prover function.
2. Set all communications options, including:
• Name
• Communication format
• Slot number
• Minor revision
• Electronic keying
• RPI - For this application, the minimum RPI = 50 ms
See pages
to
.
3. Access the module tags via the Tag Editor, see
K-Factor
Frequency
0
100
150
550
600
Содержание 1756-CFM
Страница 1: ...ControlLogix Configurable Flowmeter Module Catalog Number 1756 CFM User Manual Original Instructions...
Страница 8: ...8 Rockwell Automation Publication 1756 UM010C EN P June 2021 Notes...
Страница 118: ...118 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix B Software Configuration Tags Notes...
Страница 124: ...124 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix C Module Schematics Notes...
Страница 149: ...Rockwell Automation Publication 1756 UM010C EN P June 2021 149 ControlLogix Configurable Flowmeter Module User Manual...