26
Rockwell Automation Publication 1756-UM010C-EN-P - June 2021
Chapter 3 Configurable Flowmeter Module Features and Operational Modes
EXAMPLE
In this scenario,
Compatible Keying allows I/O communication
:
The module configuration is for a 1756-IB16D module with module
revision 2.1. The physical module is a 1756-IB16D module with module
revision 3.2. In this case, communication is allowed because the
major revision of the physical module is higher than expected and the
module determines that it is compatible with the prior major revision.
IMPORTANT
Changing electronic keying selections online can cause the I/O
communication connection to the module to be disrupted and can result in
a loss of data.
Module Configuration
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16D
Major Revision = 2
Minor Revision = 1
Physical Module
Vendor = Allen-Bradley
Product Type = Digital Input Module
Catalog Number = 1756-IB16D
Major Revision = 3
Minor Revision = 2
Communication is allowed.