Chapter 5 Configure the Configurable Flowmeter Module
5. Use ladder logic and a message instructions to send the new
configuration to your module, see
O.Total[0].Acceleration
Decimal
BOOL
Enables the Acceleration alarm on output connected to
channel 0. When the absolute acceleration exceeds the
Acceleration Alarm value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
1
I.Status[0].FillState
Decimal
SINT
Displays current state of module for channel 0. These
states are possible:
0 = Filler not active
1 = Filler Enabled only, waiting for start
2 = Timed Trickle Flow complete, not filled
3 = Full Flow (Fill mode =1)
4 = Timed Trickle Flow (Fill mode =1)
5 = Full Flow (Fill mode =0)
6 = Fill Total Target Trickle Flow
(Fill mode = 0)
7 = Fill complete
I.Status[0].TotalCounts
Decimal
DINT
Displays actual pulses counted by the counter connected
to the channel 0
I.Status[0].FillTotal
Float
REAL
Same calculation as Net Volume
during fill cycle.
I.Status[0].GrossVolume
Float
REAL
Total Counts during each Sample/K-factor x Meter
Factor as occurs on channel 0
I.Status[0].NetVolume
Float
REAL
Total Counts during each Sample/K-factor x
MeterFactor x CCF) as occurs on channel 0
I.Status[0].GrossRate
Float
REAL
Total Counts in Meter Sample/ (K-factor x Sample
Interval) x Meter Factor as occurs on channel 0
I.Status[0].NetRate
Float
REAL
Total Counts in Meter Sample/ (K-factor x Sample
Interval) x Meter Factor x CCF as occurs on channel 0
I.Ch0AccelerationAlarm
Decimal
BOOL
Displays whether acceleration alarm was set on channel 0
0 = alarm was not set
1 = alarm was set
I.Ch0OverspeedAlarm
Decimal
BOOL
Displays whether overspeed alarm was set on channel 0
0 = alarm was not set
1 = alarm was set
I.Ch0OverrangeAlarm
Decimal
BOOL
Displays whether overrange alarm was set on channel 0
0 = alarm was not set
1 = alarm was set
I.Ch0OverflowAlarm
Decimal
BOOL
Displays whether overflow alarm was set on channel 0
0 = alarm was not set
1 = alarm was set
(1) Additional Digital Filter options are now defined for Major Rev 3 and later in
.
Table 9 - Tag Changes Required for Totalizer Mode Using Filler Function
Name
Style
Data Type
Definition
Enter This
Value
Содержание 1756-CFM
Страница 1: ...ControlLogix Configurable Flowmeter Module Catalog Number 1756 CFM User Manual Original Instructions...
Страница 8: ...8 Rockwell Automation Publication 1756 UM010C EN P June 2021 Notes...
Страница 118: ...118 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix B Software Configuration Tags Notes...
Страница 124: ...124 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix C Module Schematics Notes...
Страница 149: ...Rockwell Automation Publication 1756 UM010C EN P June 2021 149 ControlLogix Configurable Flowmeter Module User Manual...