Chapter 3 Configurable Flowmeter Module Features and Operational Modes
Gross Rate
Use Gross Rate to convert total counts to rate units. The module employs a
user-defined K-factor in the conversion. The K-factor is a divisor, and the time
interval is divided by this number, as shown below.
•
If the input frequency is below 100Hz, the K-factor used is always 10.0 for
frequencies interpolated between 0-100Hz.
•
If the input frequency is between 100Hz and 200Hz, the K-factor is
interpolated as follows:
•
If the input frequency is between 200Hz and 300Hz, the K-factor is
interpolated as follows:
•
If the input frequency is greater than 300Hz, the K-factor used
is always 100.0. There is no K-factor calculation over 300Hz.
To use Gross Rate, you must set the K-factor values in Module Tags, as shown.
Gross Rate =
Total Counts in Meter Sample
Sample Interval
K-factor
x
Meter Factor
K-factor = (F
in
- 100.0) x
(71.0 - 25.0)
(200.0 - 100.0)
+ 25.0
K-factor = (F
in
- 200.0) x
(111.0 - 71.0)
(300.0 - 200.0)
+ 71.0
Name
Style
Data type
Value
Change during operation
C.Operations[0].kFactStruct.kFactorForChan[0]
Float
REAL
25.0
(1)
Yes
C.Operations[0].kFactStruct.kFactorForChan[1]
Float
REAL
25.0
Yes
C.Operations[0].kFactStruct.kFactorForChan[2]
Float
REAL
71.0
Yes
C.Operations[0].kFactStruct.kFactorForChan[3]
Float
REAL
111.0
Yes
C.Operations[0].kFactStruct.kFactorForChan[4]-
C.Operations[0].kFactStruct.kFactorForChan[12]
Float
REAL
0
Yes
C.Operations[0].kFactStruct.FreqAtKFactor[0]
Float
REAL
0.0
Yes
C.Operations[0].kFactStruct.FreqAtKFactor[1]
Float
REAL
100.0
Yes
C.Operations[0].kFactStruct.FreqAtKFactor[2]
Float
REAL
200.0
Yes
C.Operations[0].kFactStruct.FreqAtKFactor[3]
Float
REAL
300.0
Yes
C.Operations[0].kFactStruct.FreqAtKFactor[4]-
C.Operations[0].kFactStruct.FreqAtKFactor[12]
Float
REAL
0
Yes
(1) To avoid discontinuity when interpolating Gross Rate, make sure the values in C.Operations[0].kFactStruct.kFactorForChan[0] and C.Operations[0].kFactStruct.kFactorForChan[1] match.
IMPORTANT
For more information on setting values in the Module Tags, see
Содержание 1756-CFM
Страница 1: ...ControlLogix Configurable Flowmeter Module Catalog Number 1756 CFM User Manual Original Instructions...
Страница 8: ...8 Rockwell Automation Publication 1756 UM010C EN P June 2021 Notes...
Страница 118: ...118 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix B Software Configuration Tags Notes...
Страница 124: ...124 Rockwell Automation Publication 1756 UM010C EN P June 2021 Appendix C Module Schematics Notes...
Страница 149: ...Rockwell Automation Publication 1756 UM010C EN P June 2021 149 ControlLogix Configurable Flowmeter Module User Manual...