UXBM Harness and Tab Washer Installation
4200-088
9-8
Revision 1.03
Figure 12 - UXBM with Combined Resistance and Cell Temperature Readings
9.5.
Discrete Resistance Readings with no Cell Temperatures
Installing a discrete reading system utilizes a harness with part number 1102-191. This type of harness
will provide a discrete resistance reading of the cell and the adjacent connecting strap as individual
values. Reference the Figure below to identify where and what style of tab washer gets installed.
When connecting the actual wires to the tab washers it is important to note that whenever a power
connection (heavier gauge black or red wire) is being made, it must be connected to the tab washer
closest to the battery post when more than one tab washer is used.