UXBM Harness and Tab Washer Installation
4200-088
9-4
Revision 1.03
Figure 8 - Recessed Post Tab Washer Assembly
9.3.
Power Harness
There are three different types of power wiring harnesses used with the UXBM’s. These are dependent
on the type of battery system being monitored. Be sure to use the proper harness when installing the
monitoring system.
Part number
Description
1102-195
5’- 2 conductor power harness for use on 2V and 4V cells. Cannot be used in
conjunction with 1102-196 or 1102-197 on the battery being monitored.
1102-196
5’- 2 conductor power harness for use on 6V, 8V, 12V and 16V mono-blocks.
Cannot be used in conjunction with 1102-195 or 1102-197 on the same battery
being monitored.
1102-197
5’ - 3 conductor power harness for split load applications – Used for batteries
that contain three or less monoblocs typically seen in telecom or generator
start applications. Cannot be used in conjunction with 1102-195 or 1102-196 on
the same battery being monitored.