1-5. Tubing Size
(A) Single type
●
Refrigerant tubing between the indoor and outdoor units
should be kept as short as possible.
●
The lengths of the refrigerant tubes between the indoor and
outdoor units are limited by the elevation difference between
the 2 units. During tubing work, try to make both the tubing
length (L) and the difference in elevation (H1) as short as
possible. Refer to Table 1-5.
H1
Single
Main tubing L
Table 1-5
Outdoor unit type
18 type
Maximum allowable tubing length
40 m
Charge-less tubing length
(actual length)
3 – 30 m
Additional charge per 1 m
20 g
Outdoor unit type
25, 36 types
Maximum allowable tubing length
50 m
Charge-less tubing length
(actual length)
3 – 30 m
Additional charge per 1 m
40g
Outdoor unit type
48, 60 types
Maximum allowable tubing length
50 m
Charge-less tubing length
(actual length)
5 – 30 m
Additional charge per 1 m
40g
(B) Simultaneous operation multi (Twin, Triple, Double-Twin)
NOTE
Because the indoor units run simultaneously, install them within the same room.
Table 1-6
Item
Contents
Symbol
Actual
length
(m)
Single
Twin
Triple
Double-Twin
Allowable
tubing
lengths
Maximum allowable
tubing length
One-way length of tubing
from outdoor unit to the most
distant indoor unit
L
L + 1
L + 2
L + 1, L + 2
L + 3
L + L1 + 1, L + L1 + 2
L + L2 + 3, L + L2 + 4
50
Maximum distribution
tubing length
Maximum length following
the first branch point (No. 1
distribution)
–
1, 2
1, 2, 3
L1 + 1, L1 + 2
L2 + 3, L2 + 4
15
Maximum branch tubing length
Difference between the
maximum length and
minimum length in tubing
following the first branch point
–
1 > 2
1 – 2
1 > 2 > 3
1 – 2
1 – 3
2 – 3
Max: L2 + 4
Min: L1 + 1
(L2 + 4) – (L1 + 1)
10
Maximum difference between lengths of No. 1 distribution tubing
(double twin)
–
–
–
L2 > L1
L2 – L1
10
Maximum difference between lengths of No. 2 distribution tubing
(double twin)
–
–
–
2 > 1, 4 > 3
2 – 1, 4 – 3
10
Maximum
allowable
height
difference
Maximum indoor-
outdoor height
difference
If outdoor unit is higher
H1
30
If outdoor unit is lower
H1
15
Maximum height difference between indoor units
–
H2
H2, H3, H4
H2, H3, H4, H5, H6, H7
0.5
* For connection tubing sizes, refer to Table 1-6 above.
A
A
A
1
2
3
4
H1
H2
H3
H4
H6
H7
H5
L1
L2
A
1
2
2
1
3
B
H1
H1
H2
H2
H4
H3
Main
tubing L
Distribution joint No. 1
Distribution joint
No. 2
Distribution joint
(purchase separately)
A = NRF-DL16R
B = NRF-DL28R
Double-Twin
Main
tubing L
Main
tubing L
Distribution tubing
Distribution joint
Twin
Triple
NOTE
●
For refrigerant tube branches, use the optional distribution joints.
●
For cautions on the use of the optional distribution joints, be sure to refer to the provided instruction sheet. Also, be careful to install
them in the correct direction (orientation).