2
2
- 24
Design of 3-WAY FLOW LOGIC
3. Electrical Wiring
Control wiring
(C) Inter-unit (between outdoor and
indoor units) control wiring
(D) Remote control wiring
(E) Control wiring for group control
(F) Inter-outdoor unit control wiring
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
Use shielded wiring*
Use shielded wiring
Use shielded wiring
0.75 mm
2
(AWG #18)
Use shielded wiring
Max. 1,000 m
Max. 500 m
Max. 500 m (Total)
Max. 500 m
3-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the
wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and cir-
cuit breaker for overcurrent protection should be
provided in the exclusive line.
(3) To prevent possible hazards from insulation failure,
the unit must be grounded.
(4) Each wiring connection must be done in accor-
dance with the wiring system diagram. Wrong
wiring may cause the unit to misoperate or
become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no
responsibility for any damage or misoperation that
occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality to
locality. For field wiring rules, please refer to your
LOCAL ELECTRICAL CODES before beginning.
You must ensure that installation complies with all
relevant rules and regulations.
(8) To prevent malfunction of the air conditioner
caused by electrical noise, care must be taken
when wiring as follows:
●
The remote control wiring and the inter-unit control
wiring should be wired apart from the inter-unit
power wiring.
●
Use shielded wires for inter-unit control wiring
between units and ground the shield on both sides.
(9) If the power supply cord of this appliance is dam-
aged, it must be replaced by a repair shop
appointed by the manufacture, because special
purpose tools are required.
3-2. Recommended Wire Length and Wire Diameter for Power Supply System
Outdoor unit
(A) Power
s
upply
(A) Power
s
upply
Wire
s
ize
Max. len
g
th
Wire
s
ize Max. len
g
th
EFL
8
0-
3
R410
92 m
3
0 A
EFL 100-
3
R410
70 m
3
5 A
EFL 120-
3
R410
57 m
40 A
EFL 140-
3
R410
79 m
40 A
EFL 160-
3
R410
6
8
m
50 A
6 mm
6 mm
6 mm
10 mm
10 mm
6 mm
2
6 mm
2
10 mm
2
10 mm
2
10 mm
2
2
2
2
2
2
Time delay fu
s
e or
circuit capacity
Time delay fu
s
e or
circuit capacity
or
92 m
70 m
95 m
79 m
6
8
m
3
5A
3
5A
50A
50A
50A
NOTE
* With ring-type wire terminal.
Indoor unit
Time delay fu
s
e or
circuit capacity
(B) Power
s
upply
2.5 mm
2
NWFL
NK
S
FL, NK2FL, NKFL,
NPFL, NDLP
Type
M
a
x. 150 m
M
a
x. 1
3
0 m
M
a
x. 60 m
M
a
x. 50/
3
0 m
10 – 16A
10 – 16A
10 – 16A
10 – 16A
NDHPL (254,
3
64, 4
8
4)
NDHPL (764/964)
04-218 Airwell-2.qxp 01/06/2007 13:16 Page 24
Содержание EFL 100-3R410
Страница 300: ...6 6 15 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NWFL 24 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 15...
Страница 306: ...6 6 21 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 24 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 21...
Страница 308: ...6 6 23 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 36 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 23...
Страница 310: ...6 6 25 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 48 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 25...
Страница 312: ...6 6 27 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 76 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 27...
Страница 314: ...6 6 29 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 96 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 29...
Страница 315: ...6 6 30 Electrical Data 2 Indoor Unit 8 Electric Wiring Diagram ST NDHP 96 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 30...