Design of 3-WAY FLOW LOGIC
NOTE
1. Model Selecting and Capacity Calculator
1-7. Capacity Correction Graph According to Tubing Length and Elevation Difference
■
■
Capacity change characteristics
<Cooling>
Ele
v
a
tion diff
erence (m)
Base capacity
change rate
Base capacity
h
t
*1
92
90 88 86 84 82 80 78 76
94
96
98
100
%
0 10 20 30 40 50 60 70 80 90 100
110
120 130
140 150
50
40
30
20
10
0
–10
–20
–30
–40
Equivalent length (m)
Equivalent length (m)
Equivalent length (m)
Elevation dif
ference (m)
Base capacity
change rate
96
98
100
%
0 10 20 30 40 50 60 70 80 90 100
110
120 130
140 150
10 20 30 40 50 60 70 80 90 100
110
120 130
140 150
–40
50
40
30
20
10
0
–10
–20
–30
–40
94 93 92 91 90 89 88 87 86 85 84
95
97
99
<Heating>
Table of correction coefficients by horsepower (HP)
Equivalent
horsepower
50Hz
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
1.25
1.15
1.00
1.05
1.05
1.19
1.15
1.07
1.09
1.09
1.03
1.05
1.05
1.11
1.11
1.06
1.07
1.07
1.04
1.05
1.05
* The capacity change
rate due to the
refrigerant tubing length
and elevation difference
for each horsepower
level is found from the
correction coefficient
for that horsepower
from this table
multiplied by the base
capacity change rate
from the graphs at left.
However, even if the
calculated result
exceeds 100%, the
maximum capacity
change rate is 100%.
*1 Sample calculations
(System: 20 HP, 50 Hz, 50 m equivalent length, 15 m elevation
difference
The cooling capacity and heating capacity for this system are
found as shown below.)
●
Cooling operation
From the table, the correction coefficient for that horsepower
level is found to be 1.15.
From the graph, the base capacity change rate is found to be
92.0%.
92.0%
×
1.15 = 97.52%
Capacity change rate is 97.52%.
56.0kW
×
97.52% = 54.6kW
Cooling capacity is 54.6 kW.
●
Heating operation
From the table, the correction coefficient for that horsepower
level is found to be 1.06.
From the graph, the base capacity change rate is found to be
97.2%.
97.2%
×
1.06 = 103.0%
Because the calculation result exceeds 100%, the capacity
change rate is 100%.
63.0kW
×
100% = 63.0kW
Heating capacity is 63.0 kW
The positive side for the elevation difference indicates that
the outdoor unit is installed at a higher position than the
indoor units. The negative side indicates the opposite.
●
●
Inverter model rated performance values
Cooling
He
a
ting
Item
Model
Cooling
c
a
p
a
city
(kW)
Power
con
su
mption
(kW)
He
a
ting
c
a
p
a
city
(kW)
Power
con
su
mption
(kW)
<50Hz model
s
>
22.4
2
8
.0
33
.5
40.0
45.0
5.9
3
8
.12
9.
8
2
11.6
1
3
.
3
25.0
3
1.5
3
7.5
45.0
50.0
6.11
7.97
9.
8
4
11.5
1
3
.2
04-218 Airwell-2.qxp 01/06/2007 13:16 Page 16
Содержание EFL 100-3R410
Страница 300: ...6 6 15 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NWFL 24 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 15...
Страница 306: ...6 6 21 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 24 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 21...
Страница 308: ...6 6 23 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 36 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 23...
Страница 310: ...6 6 25 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 48 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 25...
Страница 312: ...6 6 27 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 76 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 27...
Страница 314: ...6 6 29 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 96 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 29...
Страница 315: ...6 6 30 Electrical Data 2 Indoor Unit 8 Electric Wiring Diagram ST NDHP 96 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 30...