Design of 3-WAY FLOW LOGIC
1. Model Selecting and Capacity Calculator
1-3. Design of Tubing Length
Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
R410A distribution joint
Note: Do not use commercially available T-joints for the liquid tubing and parts.
* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor unit connections and tubing branches.
(ø9.52)
Balance tubing
Max. 40cm
Max. 40cm
For
extension
For
extension
T-joint tubing
(header joint system)
Solenoid valve kit
Explanation of symbols
Distribution joint
(APR: purchased separately)
Ball valve (field supply)
T-joint (field supply)
Solidly welded shut
(pinch weld)
1.
2.
Main tubing length LM = LA + LB …
≤
80 m
Main distribution tubes LC – LH are selected according to the capacity after the
distribution joint.
3.
4.
Sizes of indoor unit connection tubing 1 – 40 are determined by the connection
tubing sizes on the indoor units.
The outdoor connection main tubing (LD portion) is determined by the total capacity of the outdoor
units that are connected to the tube ends.
Items
Marks
Contents
Length (m)
L1
Max. tubing length
Actual length
150
Equivalent length
175
Δ
L (L2 – L4)
Difference between max. length and min.
40
length from the No.1 distribution joint
LM
Max. length of main tubing (at max. diameter)
80
1
,
2
~
40
Max. length of each distribution tube
30
L1+
1
+
2
+~
40
Total max. tubing length including length of
300
A
+
B
+LF+LG+LH
each distribution tube (only narrow tubing)
L5
L3
Distance between outdoor units
10
H1
When outdoor unit is installed higher than indoor unit
50
When outdoor unit is installed lower than indoor unit
40
H2
Max. difference between indoor units
15
H3
Max. difference between outdoor units
4
L = Length, H = Height
Allowable tubing
length
>
>
Allowable elevation
difference
>
>
>
>
>
>
>
>
>
+
*3
2
Allowable length of
joint tubing
T-joint tubing (field-supply); Max. tubing length between
the first T-joint and solidly welded-shut end point
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown
in the figure below.
04-218 Airwell-2.qxp 01/06/2007 13:15 Page 4
Содержание EFL 100-3R410
Страница 300: ...6 6 15 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NWFL 24 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 15...
Страница 306: ...6 6 21 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 24 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 21...
Страница 308: ...6 6 23 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 36 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 23...
Страница 310: ...6 6 25 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 48 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 25...
Страница 312: ...6 6 27 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 76 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 27...
Страница 314: ...6 6 29 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 96 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 29...
Страница 315: ...6 6 30 Electrical Data 2 Indoor Unit 8 Electric Wiring Diagram ST NDHP 96 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 30...