3-WAY FLOW LOGIC Unit Specifications
6. Concealed Duct Type
6-5. Increasin
g
the Fan Speed
If external static pressure is too great (due to long
extension of ducts, for example), the air flow volume
may drop too low at each air outlet. This problem may
be solved by increasing the fan speed using the
following procedure:
(1)
Remove 2 screws on the electrical component
box and remove the cover plate.
(2)
Disconnect the fan motor sockets in the box.
(3)
Take out the booster cable (sockets at both ends)
clamped in the box.
(4)
Securely connect the booster cable sockets
between the disconnected fan motor sockets in
step 2 as shown in the Fig. 7-1.
(5)
Place the cable neatly in the box and reinstall the
cover plate.
Booster cable
Booster cable
Electrical component box
(At shipment)
(Connected booster cable)
1743_M_I
Fan motor socket
Fan
motor
Indoor Fan Performance
25 Type
48 Type
36 Type
Fig. 7-2
20
Air Flow Volume (m
3
/minute)
External Static Pressure
0
50
0
5
10
15
150
10
Limit line
Limit line
HT
H
L
100
I
M
(mmAq)
(Pa)
30
25
40
Air Flow Volume (m
3
/minute)
External Static Pressure
0
50
0
5
5.6
3.8
10
15
150
20
Limit line
Limit line
L
100
M
H
(mmAq)
(Pa)
HT
30
Air Flow Volume (m
3
/minute)
External Static Pressure
0
50
0
5
6.6
5.4
2.4
3.7
14 16
10
15
150
20
21
26
L
imit line
HT
L
100
M
H
Limit line
(mmAq)
(Pa)
HT : Using the booster cable
H : At shipment
NOTE
■
How to read the diagram
The vertical axis is the external static pressure (Pa) while the horizontal axis represents the AIR FLOW (m
3
/minute). The
characteristic curves for “HT”, “H”, “M” and “L” fan speed control are shown.
The nameplate values are shown based on the “H” air flow. For the 25 type, the air flow is 18 m
3
/minute, while the
external static pressure is 49 Pa at “H” position. If external static pressure is too great (due to long extension of duct, for
example), the air flow volume may drop too low at each air outlet.
This problem may be solved by increasing the fan speed as explained above.
Fig. 7-1
18 Type
7, 9, 12 Type
5
7
8.5
Air Flow (m
3
/minute)
External Static Pressure
0
50
100
0
5
4.4
4.9
10
15
150
10
(mmAq)
(Pa)
Limit line
Limit line
HT
H
M
L
15
Air Flow (m
3
/minute)
External Static Pressure
0
50
0
5
2.5
3.9
10
15
150
10
10.5
9
12
Limit line
Limit line
HT
M
L
100
H
(mmAq)
(Pa)
04-218 Airwell-4_6-7.qxp 01/06/2007 13:24 Page 106
Содержание EFL 100-3R410
Страница 300: ...6 6 15 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NWFL 24 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 15...
Страница 306: ...6 6 21 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 24 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 21...
Страница 308: ...6 6 23 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 36 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 23...
Страница 310: ...6 6 25 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 48 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 25...
Страница 312: ...6 6 27 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 76 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 27...
Страница 314: ...6 6 29 Electrical Data 2 Indoor Unit Schematic Wiring Diagram ST NDHP 96 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 29...
Страница 315: ...6 6 30 Electrical Data 2 Indoor Unit 8 Electric Wiring Diagram ST NDHP 96 04 218 Airwell 6 qxp 01 06 2007 13 23 Page 30...