Technical Data
Ecodesign - DCC (XQ)
Notes Units
DCC043DX-10KSS0
DCC044DX-10KSQ0
DCC044DX-12LXX0
DCC044DX-12KSS0
SEPR
1, 3, 5
6.76
6.62
6.19
7.05
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
467900.34
491915.27
520999.94
458245.56
Rated Refrigerant Capacity P
A
1, 3, 5
kW
427.10
439.80
435.40
435.90
Rated Power Input D
A
kW
134.73
140.06
129.97
130.90
Rated EER
DC,A
3.17
3.14
3.35
3.33
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
402.8 / 333.5
415.7 / 301.6
479.5 / 401.5
408.6 / 336.0
Declared Power Input D
B
kW
90.7 / 70.9
94.9 / 63.6
106.2 / 87.3
87.9 / 69.1
Declared EER
DC,B
4.44 / 4.70
4.38 / 4.74
4.52 / 4.60
4.65 / 4.87
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
436.5 / 359.3
448.5 / 322.8
434.9 / 350.6
442.2 / 361.7
Declared Power Input D
C
kW
72.9 / 57.4
75.7 / 51.7
72.2 / 56.6
70.2 / 55.6
Declared EER
DC,C
5.99 / 6.26
5.93 / 6.24
6.02 / 6.20
6.30 / 6.51
Declared Refrigerant Capacity
P
D
kW
384.9 / 291.7
478.5 / 343.1
358.8 / 269.0
386.7 / 292.6
Declared Power Input D
D
kW
43.5 / 32.5
56.1 / 39.4
50.3 / 38.0
41.7 / 31.3
Declared EER
DC,D
8.85 / 8.99
8.54 / 8.70
7.13 / 7.07
9.28 / 9.35
SSCEE
2, 3, 5
%
198
194
190
203
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
427.50
440.20
435.90
436.30
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
427.10
439.80
435.40
435.90
Declared EER
d
35°C
3.17
3.14
3.35
3.33
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
402.8 / 333.5
415.7 / 301.6
479.5 / 401.5
408.6 / 336.0
Declared EER
d
30°C
4.44 / 4.70
4.38 / 4.74
4.52 / 4.60
4.65 / 4.87
Declared Cooling Capacity
25°C Pdc
kW
436.5 / 359.3
448.5 / 322.8
434.9 / 350.6
442.2 / 361.7
Declared EER
d
25°C
5.99 / 6.26
5.93 / 6.24
6.02 / 6.20
6.30 / 6.51
Declared Cooling Capacity
20°C Pdc
kW
384.9 / 291.7
478.5 / 343.1
358.8 / 269.0
386.7 / 292.6
Declared EER
d
20°C
8.85 / 8.99
8.54 / 8.70
7.13 / 7.07
9.28 / 9.35
Sound Power Level L
dB(A)
86.83
87.38
86.43
86.86
Air fl ow rate
m³/h
144205.38
144205.38
192170.78
173046.46
Off mode P
OFF
0.08
0.08
0.14
0.08
Thermostat-off mode P
TO
1.90
2.04
1.93
2.11
Standby Mode P
SB
0.14
0.14
0.27
0.15
Crankcase heater mode P
CK
0.13
0.11
0.00
0.13
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
123
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020