Technical Data
Ecodesign - DCC (RQ)
Notes Units
DCC044DR-10KSS0
DCC045DR-10KSQ0
DCC048DR-09NXY0
DCC056DR-10NYY0
SEPR
1, 3, 5
6.75
6.64
5.77
5.74
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
479749.38
503195.24
620987.04
718324.68
Rated Refrigerant Capacity P
A
1, 3, 5
kW
437.10
450.80
483.40
556.10
Rated Power Input D
A
kW
134.91
140.00
160.60
184.14
Rated EER
DC,A
3.24
3.22
3.01
3.02
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
479.6 / 406.6
493.4 / 420.3
530.6 / 434.2
609.7 / 511.3
Declared Power Input D
B
kW
110.6 / 90.8
114.6 / 94.8
131.2 / 103.8
151.0 / 123.4
Declared EER
DC,B
4.34 / 4.48
4.31 / 4.43
4.04 / 4.18
4.04 / 4.15
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
439.8 / 359.3
452.3 / 322.8
469.4 / 388.2
552.8 / 446.5
Declared Power Input D
C
kW
72.9 / 57.5
75.5 / 51.8
85.7 / 68.5
102.1 / 79.2
Declared EER
DC,C
6.03 / 6.25
5.99 / 6.23
5.48 / 5.67
5.41 / 5.64
Declared Refrigerant Capacity
P
D
kW
384.9 / 291.7
481.9 / 343.1
403.0 / 290.3
464.2 / 348.0
Declared Power Input D
D
kW
43.6 / 32.5
55.5 / 39.5
58.7 / 41.9
67.9 / 51.0
Declared EER
DC,D
8.83 / 8.96
8.68 / 8.68
6.87 / 6.93
6.84 / 6.83
SSCEE
2, 3, 5
%
197
194
180
177
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
437.50
451.30
483.80
556.60
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
437.10
450.80
483.40
556.10
Declared EER
d
35°C
3.24
3.22
3.01
3.02
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
479.6 / 406.6
493.4 / 420.3
530.6 / 434.2
609.7 / 511.3
Declared EER
d
30°C
4.34 / 4.48
4.31 / 4.43
4.04 / 4.18
4.04 / 4.15
Declared Cooling Capacity
25°C Pdc
kW
439.8 / 359.3
452.3 / 322.8
469.4 / 388.2
552.8 / 446.5
Declared EER
d
25°C
6.03 / 6.25
5.99 / 6.23
5.48 / 5.67
5.41 / 5.64
Declared Cooling Capacity
20°C Pdc
kW
384.9 / 291.7
481.9 / 343.1
403.0 / 290.3
464.2 / 348.0
Declared EER
d
20°C
8.83 / 8.96
8.68 / 8.68
6.87 / 6.93
6.84 / 6.83
Sound Power Level L
dB(A)
93.81
95.69
89.56
90.08
Air fl ow rate
m³/h
232965.67
232965.67
209669.11
232965.67
Off mode P
OFF
0.08
0.08
0.14
0.14
Thermostat-off mode P
TO
2.01
2.16
1.38
2.01
Standby Mode P
SB
0.14
0.14
0.26
0.26
Crankcase heater mode P
CK
0.13
0.11
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
108
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020