Technical Data
Ecodesign - DCC (RQ)
Notes Units
DCC049DR-1
1NXY0
DCC056DR-12NYY0
DCC058DR-12NYV0
DCC062TR-1
1PNXX
SEPR
1, 3, 5
5.93
5.89
5.76
5.60
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
611107.88
707371.52
747470.33
815811.97
Rated Refrigerant Capacity P
A
1, 3, 5
kW
489.20
562.50
580.80
616.80
Rated Power Input D
A
kW
155.30
178.01
189.19
208.38
Rated EER
DC,A
3.15
3.16
3.07
2.96
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
536.4 / 438.7
616.7 / 516.7
636.6 / 529.9
605.7 / 531.0
Declared Power Input D
B
kW
126.5 / 100.4
145.9 / 119.5
154.2 / 124.7
149.1 / 128.4
Declared EER
DC,B
4.24 / 4.37
4.23 / 4.32
4.13 / 4.25
4.06 / 4.13
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
474.0 / 391.4
558.1 / 450.1
569.9 / 462.1
573.2 / 490.0
Declared Power Input D
C
kW
82.9 / 66.6
98.9 / 77.1
102.9 / 81.1
105.7 / 90.1
Declared EER
DC,C
5.72 / 5.88
5.64 / 5.84
5.54 / 5.70
5.42 / 5.44
Declared Refrigerant Capacity
P
D
kW
402.9 / 290.3
464.2 / 348.0
475.3 / 353.2
511.5 / 423.2
Declared Power Input D
D
kW
58.1 / 41.6
67.2 / 50.6
70.6 / 52.4
76.8 / 64.2
Declared EER
DC,D
6.94 / 6.98
6.91 / 6.88
6.73 / 6.74
6.66 / 6.59
SSCEE
2, 3, 5
%
186
183
176
173
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
489.60
563.00
581.30
617.20
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
489.20
562.50
580.80
616.80
Declared EER
d
35°C
3.15
3.16
3.07
2.96
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
536.4 / 438.7
616.7 / 516.7
636.6 / 529.9
605.7 / 531.0
Declared EER
d
30°C
4.24 / 4.37
4.23 / 4.32
4.13 / 4.25
4.06 / 4.13
Declared Cooling Capacity
25°C Pdc
kW
474.0 / 391.4
558.1 / 450.1
569.9 / 462.1
573.2 / 490.0
Declared EER
d
25°C
5.72 / 5.88
5.64 / 5.84
5.54 / 5.70
5.42 / 5.44
Declared Cooling Capacity
20°C Pdc
kW
402.9 / 290.3
464.2 / 348.0
475.3 / 353.2
511.5 / 423.2
Declared EER
d
20°C
6.94 / 6.98
6.91 / 6.88
6.73 / 6.74
6.66 / 6.59
Sound Power Level L
dB(A)
88.07
88.58
89.69
91.09
Air fl ow rate
m³/h
256262.24
279558.81
279558.81
256262.24
Off mode P
OFF
0.14
0.14
0.14
0.15
Thermostat-off mode P
TO
1.39
2.03
2.44
1.27
Standby Mode P
SB
0.27
0.27
0.27
0.30
Crankcase heater mode P
CK
0.00
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
110
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020