Fre
eC
oo
l
59
DeltaChill Technical Manual 9758541 V1.1_06_2020
Chillers
DeltaChill
TM
Technical Data
DCF Regular Quiet
Mechanical Data
Notes Units
DCF095TR-
15R
YVV
DCF098TR-
15R
VVV
DCF101TR- 15R
VVW
DCF104TR- 15R
VWW
DCF107TR- 15R
WWW
DCF070TR-
17RNXX
Capacity
Number of Refrigeration Circuits
3
3
3
3
3
3
Cooling Duty - EC Fans
(1)
kW
953.5
976.4
1006.7
1037.2
1067.7
701.0
Nominal Input - Mechanical
kW
310.0
321.4
336.2
350.9
365.6
199.9
EER
(2)
3.08
3.04
2.99
2.96
2.92
3.51
ESEER (Gross)
4.45
4.45
4.42
4.40
4.35
4.72
ESEER (Net)
4.05
4.08
4.04
4.01
3.95
4.38
Nominal Output - Free Cooling
kW
679.29
682.42
686.47
690.48
694.53
680.95
Ambient temperature for 100% Free Cooling (5)
°C
-1.90
-2.20
-2.60
-3.10
-3.50
2.60
Capacity Steps
% 11-23-35-46-57-
68-79-89-100
12-23-35-46-
57-68-79-89-
100
11-23-35-46-57-
69-79-89-100
11-23-36-46-57-
69-79-89-100
12-24-36-47-
58-69-79-90-
100
16-28-40-56-
67-78-89-100
Minimum Turndown Ratio
0.11
0.12
0.11
0.11
0.12
0.16
Dimensions (HxW)
mm
2682x2200
Length
mm
9374
9374
9374
9374
9374
10506
Machine Weight
(3)
kg
8425
8450
8505
8560
8615
8770
Operating Weight
kg
9050
9075
9130
9185
9240
9485
Evaporator
Shell and Tube
Water Volume (Total Internal)
l
508.0
492.5
492.5
492.5
492.5
538.0
Maximum Waterfl ow
l/s
65.0
85.9
85.9
85.9
85.9
52.1
Minimum Waterfl ow
l/s
14.9
19.9
19.9
19.9
19.9
12.0
Condenser
Face Area (Total)
m²
35.63
35.63
35.63
35.63
35.63
40.38
Nominal Airfl ow
m³/s
88.73
88.73
88.73
88.73
88.73
100.56
Condenser Fan & Motor
Quantity
15
15
15
15
15
17
Diameter
mm
800
800
800
800
800
800
Maximum Speed
rpm
1026
1026
1026
1026
1026
1026
Compressor
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio
+ Trio
Quantity of Compressors
9
9
9
9
9
8
Oil Charge Volume (Total)
l
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
2x5.3 + 3x5.3 +
3x5.3
Oil Type
Polyvinyl Ether
Refrigeration
GWP Equivalent CO
2
Tonnes
tCO
2
70.20
72.23
72.23
72.23
72.23
62.78
Charge (Total)
kg
31 + 36 + 37
32 + 37 + 38
32 + 37 + 38
32 + 37 + 38
32 + 37 + 38
26 + 33 + 34
Maximum Allowable Pressure High Side (PS)
barg
40.2
40.2
40.2
40.2
40.2
40.2
Maximum Allowable Pressure Low Side (PS)
barg
25.9
25.9
25.9
25.9
25.9
25.9
Connections
Water Inlet / Outlet - Unit
DN150
DN150
DN150
DN150
DN150
DN150
Water System
Minimum System Water Volume
(4)
l
1934.11
2081.82
2081.77
2081.77
2305.19
2096.10
Nominal Water Flow
l/s
48.12
49.27
50.80
52.34
53.88
35.38
Pressure drop
kPa
146.93
130.98
138.19
145.63
153.27
104.50
Electrical Data
Nominal Run Amps
(6)
A
604.6
625.0
645.5
666.1
283.5
437.1
Maximum Start Amps
A
870
884
904
894
453
606
Recommended Mains Fuse Size
A
630
670
670
710
315
500
Recommended Permanent Fuse Size
A
16
16
16
16
16
16
Maximum Permanent Incoming Cable Size
mm²
4
4
4
4
4
4
Evaporator Heater Rating
W
250
250
250
250
170
250
Condenser Fan - Per Fan (EC)
Full Load Amps
A
3.9
3.9
3.9
3.9
3.9
3.9
Motor Rating
kW
2.56
2.56
2.56
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
60.4 / 60.4 /
60.4
60.4 / 60.4 /
67.3
60.4 / 67.3 /
67.3
67.3 / 67.3 /
67.3
40.7 / 40.7
40.7 / 40.7 /
40.7
Quantity
(7)
3
3
3
3
2
3
Motor Rating
kW
36.5 / 36.5 /
36.5
36.5 / 36.5 /
41.3
36.5 / 41.3 /
41.3
41.3 / 41.3 /
41.3
25.9 / 25.9
25.9 / 25.9 /
25.9
Start Amps
(8)
A
326 / 326 / 326 326 / 326 / 295 326 / 295 / 295 295 / 295 / 295
210 / 210
210 / 210 / 210
(1)
Based on FC units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% ethylene glycol. All performance data is supplied in
accordance with BS EN 14511-1:2018.
(2)
EER = DX Cooling Output / (Compressor input power + Fan Input Power).
(3)
Based on standard unit without options, operating weight includes refrigerant charge and water volume. For unit weights with waterside options fi tted
please refer to Airedale.
(4)
For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5)
Ambient temperature that full Freecool capacity can be achieved.
(6)
EC fans and no pumps.
(7)
Data quoted at design fl ow-rate, 7°C supply temperature and 35°C ambient, 100% water.
(8)
Starting amps refers to the direct on line connections.
Pump electrical data is available from Airedale upon request.
Technical Data
DCF Regular Quiet
Mechanical Data
Notes Units
DCF071TR-
18RXXX
DCF085TR-
17RXYY
DCF092TR-
18R
YYY
DCF097TR-
18R
YVV
DCF100TR-
18R
VVV
DCF103TR- 18R
VVW
Capacity
Number of Refrigeration Circuits
3
3
3
3
3
3
Cooling Duty - EC Fans
(1)
kW
713.8
845.9
919.1
970.3
996.5
1030.7
Nominal Input - Mechanical
kW
200.5
253.4
276.5
299.2
310.6
325.2
EER
(2)
3.56
3.34
3.32
3.24
3.21
3.17
ESEER (Gross)
4.91
4.70
4.56
4.60
4.60
4.58
ESEER (Net)
4.54
4.31
4.23
4.21
4.24
4.21
Nominal Output - Free Cooling
kW
709.58
726.58
775.00
786.22
791.37
797.60
Ambient temperature for 100% Free Cooling (5)
°C
2.90
1.00
0.70
0.10
-0.20
-0.60
Capacity Steps
% 11-23-34-45-57-
68-78-89-100
10-22-35-44-
56-68-77-88-
100
12-23-35-46-
57-68-79-89-
100
11-23-35-45-57-
68-78-89-100
12-23-35-46-
57-68-79-89-
100
11-22-35-45-56-
68-78-89-100
Minimum Turndown Ratio
0.11
0.10
0.12
0.11
0.12
0.11
Dimensions (HxW)
mm
2682x2200
Length
mm
10506
10506
10506
10506
10506
10506
Machine Weight
(3)
kg
9055
9010
9200
9195
9215
9270
Operating Weight
kg
9770
9720
9920
9915
9940
9995
Evaporator
Shell and Tube
Water Volume (Total Internal)
l
538.0
523.0
508.0
508.0
492.5
492.5
Maximum Waterfl ow
l/s
52.1
65.0
85.9
65.0
85.9
85.9
Minimum Waterfl ow
l/s
12.0
14.9
19.9
14.9
19.9
19.9
Condenser
Face Area (Total)
m²
42.75
40.38
42.75
42.75
42.75
42.75
Nominal Airfl ow
m³/s
106.48
100.56
106.48
106.48
106.48
106.48
Condenser Fan & Motor
Quantity
18
17
18
18
18
18
Diameter
mm
800
800
800
800
800
800
Maximum Speed
rpm
1026
1026
1026
1026
1026
1026
Compressor
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Trio + Trio +
Trio
Quantity of Compressors
9
9
9
9
9
9
Oil Charge Volume (Total)
l
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
3x5.3 + 3x5.3 +
3x5.3
Oil Type
Polyvinyl Ether
Refrigeration
GWP Equivalent CO
2
Tonnes
tCO
2
64.80
69.53
75.60
75.60
78.30
78.30
Charge (Total)
kg
29 + 33 + 34
28 + 37 + 38
34 + 38 + 40
34 + 38 + 40
35 + 40 + 41
35 + 40 + 41
Maximum Allowable Pressure High Side (PS)
barg
40.2
40.2
40.2
40.2
40.2
40.2
Maximum Allowable Pressure Low Side (PS)
barg
25.9
25.9
25.9
25.9
25.9
25.9
Connections
Water Inlet / Outlet - Unit
DN150
DN150
DN150
DN150
DN150
DN150
Water System
Minimum System Water Volume
(4)
l
1488.95
1496.80
1930.04
1948.29
2098.01
2097.95
Nominal Water Flow
l/s
36.02
42.69
46.38
48.97
50.29
52.02
Pressure drop
kPa
105.04
126.80
111.27
135.93
119.43
126.73
Electrical Data
Nominal Run Amps
(6)
A
480.4
554.9
596.0
616.9
637.3
657.7
Maximum Start Amps
A
753
827
862
882
896
916
Recommended Mains Fuse Size
A
560
630
630
670
670
710
Recommended Permanent Fuse Size
A
16
16
16
16
16
16
Maximum Permanent Incoming Cable Size
mm²
4
4
4
4
4
4
Evaporator Heater Rating
W
250
250
250
250
250
250
Condenser Fan - Per Fan (EC)
Full Load Amps
A
3.9
3.9
3.9
3.9
3.9
3.9
Motor Rating
kW
2.56
2.56
2.56
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
40.7 / 40.7 /
53.7
53.7 / 53.7 /
53.7
53.7 / 60.4 /
60.4
60.4 / 60.4 /
60.4
60.4 / 60.4 /
67.3
60.4 / 67.3 /
67.3
Quantity
(7)
3
3
3
3
3
3
Motor Rating
kW
25.9 / 25.9 /
33.6
33.6 / 33.6 /
33.6
33.6 / 36.5 /
36.5
36.5 / 36.5 /
36.5
36.5 / 36.5 /
41.3
36.5 / 41.3 /
41.3
Start Amps
(8)
A
210 / 210 / 326 326 / 326 / 326 326 / 326 / 326 326 / 326 / 326 326 / 326 / 295 326 / 295 / 295
(1)
Based on FC units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% ethylene glycol. All performance data is supplied in
accordance with BS EN 14511-1:2018.
(2)
EER = DX Cooling Output / (Compressor input power + Fan Input Power).
(3)
Based on standard unit without options, operating weight includes refrigerant charge and water volume. For unit weights with waterside options fi tted
please refer to Airedale.
(4)
For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5)
Ambient temperature that full Freecool capacity can be achieved.
(6)
EC fans and no pumps.
(7)
Data quoted at design fl ow-rate, 7°C supply temperature and 35°C ambient, 100% water.
(8)
Starting amps refers to the direct on line connections.
Pump electrical data is available from Airedale upon request.