Technical Data
Ecodesign - DCC (RQ)
Notes Units
DCC01
1DR-04JBC0
DCC016DR-04JGG0
DCC021DR-04JJK0
DCC026DR-04KKL0
SEPR
1, 3, 5
8
6
6
6
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
104743
175957
241463
322701
Rated Refrigerant Capacity P
A
1, 3, 5
kW
106.4
152.9
204.1
258.0
Rated Power Input D
A
kW
30.0
49.3
66.9
88.4
Rated EER
DC,A
3.55
3.10
3.05
2.92
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
116.5 / 49.9
167.0 / 128.1
224.0 / 164.9
284.8 / 214.1
Declared Power Input D
B
kW
24.1 / 9.9
39.6 / 29.1
54.9 / 37.6
73.1 / 51.7
Declared EER
DC,B
4.84 / 5.06
4.22 / 4.41
4.08 / 4.38
3.89 / 4.14
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
126.0 / 54.0
137.3 / 95.0
177.5 / 128.1
231.1 / 163.5
Declared Power Input D
C
kW
18.7 / 7.6
23.1 / 15.1
30.4 / 21.3
42.4 / 28.5
Declared EER
DC,C
6.72 / 7.11
5.95 / 6.31
5.84 / 6.02
5.46 / 5.74
Declared Refrigerant Capacity
P
D
kW
135.0 / 57.7
145.8 / 100.3
189.6 / 136.2
247.9 / 174.3
Declared Power Input D
D
kW
13.7 / 5.7
17.8 / 12.0
23.8 / 17.0
32.9 / 22.8
Declared EER
DC,D
9.87 / 10.07
8.18 / 8.37
7.98 / 8.02
7.52 / 7.66
SSCEE
2, 3, 5
%
193
187
184
174
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
106.5
153.1
204.4
258.3
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
106.4
152.9
204.1
258.0
Declared EER
d
35°C
3.55
3.10
3.05
2.92
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
116.5 / 49.9
167.0 / 128.1
224.0 / 164.9
284.8 / 214.1
Declared EER
d
30°C
4.84 / 5.06
4.22 / 4.41
4.08 / 4.38
3.89 / 4.14
Declared Cooling Capacity
25°C Pdc
kW
126.0 / 54.0
137.3 / 95.0
177.5 / 128.1
231.1 / 163.5
Declared EER
d
25°C
6.72 / 7.11
5.95 / 6.31
5.84 / 6.02
5.46 / 5.74
Declared Cooling Capacity
20°C Pdc
kW
135.0 / 57.7
145.8 / 100.3
189.6 / 136.2
247.9 / 174.3
Declared EER
d
20°C
9.87 / 10.07
8.18 / 8.37
7.98 / 8.02
7.52 / 7.66
Sound Power Level L
dB(A)
86
85
90
92
Air fl ow rate
m³/h
93186
93186
93186
93186
Off mode P
OFF
0.08
0.08
0.08
0.08
Thermostat-off mode P
TO
0.24
0.44
0.73
0.87
Standby Mode P
SB
0.11
0.11
0.11
0.11
Crankcase heater mode P
CK
0.04
0.09
0.09
0.09
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Technical Data
Ecodesign - DCC (RQ)
Notes Units
DCC01
1DR-06JBC0
DCC016DR-06JGG0
DCC021DR-06JJK0
DCC027DR-06KKL0
SEPR
1, 3, 5
8.21
7.11
6.94
6.64
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
97622.63
162636.78
223074.38
297514.50
Rated Refrigerant Capacity P
A
1, 3, 5
kW
108.10
156.00
208.80
266.50
Rated Power Input D
A
kW
28.52
46.43
62.89
82.51
Rated EER
DC,A
3.79
3.36
3.32
3.23
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
118.3 / 50.6
170.3 / 130.4
229.0 / 168.1
292.9 / 218.9
Declared Power Input D
B
kW
22.7 / 9.3
36.7 / 27.1
50.9 / 35.1
67.8 / 48.1
Declared EER
DC,B
5.22 / 5.44
4.64 / 4.81
4.50 / 4.79
4.32 / 4.55
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
127.9 / 54.7
139.7 / 96.1
248.1 / 180.9
236.3 / 166.3
Declared Power Input D
C
kW
17.3 / 7.1
21.2 / 14.1
40.1 / 28.0
38.7 / 26.5
Declared EER
DC,C
7.39 / 7.71
6.59 / 6.82
6.19 / 6.47
6.10 / 6.27
Declared Refrigerant Capacity
P
D
kW
135.8 / 58.4
148.3 / 101.4
193.1 / 138.0
253.5 / 177.1
Declared Power Input D
D
kW
12.4 / 5.3
16.0 / 11.1
21.4 / 15.7
29.0 / 20.7
Declared EER
DC,D
10.92 / 11.01
9.25 / 9.15
9.01 / 8.81
8.76 / 8.54
SSCEE
2, 3, 5
%
208
201
198
190
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
108.20
156.20
209.20
266.90
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
108.10
156.00
208.80
266.50
Declared EER
d
35°C
3.79
3.36
3.32
3.23
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
118.3 / 50.6
170.3 / 130.4
229.0 / 168.1
292.9 / 218.9
Declared EER
d
30°C
5.22 / 5.44
4.64 / 4.81
4.50 / 4.79
4.32 / 4.55
Declared Cooling Capacity
25°C Pdc
kW
127.9 / 54.7
139.7 / 96.1
248.1 / 180.9
236.3 / 166.3
Declared EER
d
25°C
7.39 / 7.71
6.59 / 6.82
6.19 / 6.47
6.10 / 6.27
Declared Cooling Capacity
20°C Pdc
kW
135.8 / 58.4
148.3 / 101.4
193.1 / 138.0
253.5 / 177.1
Declared EER
d
20°C
10.92 / 11.01
9.25 / 9.15
9.01 / 8.81
8.76 / 8.54
Sound Power Level L
dB(A)
86.17
84.30
89.47
91.83
Air fl ow rate
m³/h
139779.40
139779.40
139779.40
139779.40
Off mode P
OFF
0.08
0.08
0.08
0.08
Thermostat-off mode P
TO
0.26
0.49
0.80
0.94
Standby Mode P
SB
0.12
0.12
0.12
0.12
Crankcase heater mode P
CK
0.04
0.09
0.09
0.09
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od