Technical Data
Ecodesign - DCF (RQ)
Notes Units
DCF092TR-18R
YYY
DCF097TR-18R
YVV
DCF100TR-18R
VVV
DCF103TR-18R
VVW
SEPR
1, 3, 5
6.15
6.16
6.17
6.15
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
1004035.18
1081532.14
1124835.19
1167709.94
Rated Refrigerant Capacity P
A
1, 3, 5
kW
833.20
899.40
936.60
968.80
Rated Power Input D
A
kW
274.98
299.80
312.20
326.20
Rated EER
DC,A
3.03
3.00
3.00
2.97
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
815.3 / 716.6
878.7 / 769.9
918.0 / 807.3
942.1 / 831.9
Declared Power Input D
B
kW
198.3 / 171.2
214.6 / 183.8
223.6 / 192.7
231.3 / 200.5
Declared EER
DC,B
4.11 / 4.19
4.10 / 4.19
4.10 / 4.19
4.07 / 4.15
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
773.7 / 667.1
828.3 / 718.3
868.6 / 749.1
898.8 / 779.4
Declared Power Input D
C
kW
142.0 / 119.5
152.4 / 129.6
159.4 / 134.0
166.0 / 140.5
Declared EER
DC,C
5.45 / 5.58
5.44 / 5.54
5.45 / 5.59
5.41 / 5.55
Declared Refrigerant Capacity
P
D
kW
665.7 / 575.7
718.7 / 617.7
748.4 / 648.0
774.2 / 666.2
Declared Power Input D
D
kW
81.0 / 86.2
86.3 / 92.8
90.3 / 96.2
93.1 / 98.6
Declared EER
DC,D
8.21 / 6.68
8.33 / 6.66
8.29 / 6.73
8.32 / 6.75
SSCEE
2, 3, 5
%
171
166
171
169
SSCEE Tier
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
834.00
900.30
937.40
969.70
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
833.20
899.40
936.60
968.80
Declared EER
d
35°C
3.03
3.00
3.00
2.97
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
815.3 / 716.6
878.7 / 769.9
918.0 / 807.3
942.1 / 831.9
Declared EER
d
30°C
4.11 / 4.19
4.10 / 4.19
4.10 / 4.19
4.07 / 4.15
Declared Cooling Capacity
25°C Pdc
kW
773.7 / 667.1
828.3 / 718.3
868.6 / 749.1
898.8 / 779.4
Declared EER
d
25°C
5.45 / 5.58
5.44 / 5.54
5.45 / 5.59
5.41 / 5.55
Declared Cooling Capacity
20°C Pdc
kW
665.7 / 575.7
718.7 / 617.7
748.4 / 648.0
774.2 / 666.2
Declared EER
d
20°C
8.21 / 6.68
8.33 / 6.66
8.29 / 6.73
8.32 / 6.75
Sound Power Level L
dB(A)
90.50
92.04
92.68
93.26
Air fl ow rate
m³/h
383315.49
383315.49
383315.49
383315.49
Off mode P
OFF
0.15
0.15
0.15
0.15
Thermostat-off mode P
TO
4.80
6.23
6.02
6.53
Standby Mode P
SB
0.35
0.35
0.35
0.35
Crankcase heater mode P
CK
0.00
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.