Technical Data
Ecodesign - DCF (XQ)
Notes Units
DCF061DX-14MYY0
DCF046DX-12LXX0
DCF047DX-12KSS0
DCF049DX-12KSQ0
SEPR
1, 3, 5
6.85
6.89
7.66
7.49
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
611990.23
458508.46
418733.19
441087.56
Rated Refrigerant Capacity P
A
1, 3, 5
kW
565.70
426.60
432.70
445.60
Rated Power Input D
A
kW
177.34
132.07
134.80
140.13
Rated EER
DC,A
3.19
3.23
3.21
3.18
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
625.5 / 525.4
471.5 / 395.0
405.7 / 334.0
418.7 / 302.0
Declared Power Input D
B
kW
145.4 / 119.7
108.1 / 89.0
91.5 / 72.1
95.5 / 65.0
Declared EER
DC,B
4.30 / 4.39
4.36 / 4.44
4.44 / 4.63
4.38 / 4.65
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
569.7 / 459.7
427.6 / 344.7
439.2 / 359.6
451.1 / 323.0
Declared Power Input D
C
kW
99.7 / 78.2
73.9 / 58.1
73.8 / 58.6
76.3 / 53.1
Declared EER
DC,C
5.72 / 5.88
5.78 / 5.93
5.95 / 6.13
5.91 / 6.08
Declared Refrigerant Capacity
P
D
kW
451.9 / 354.7
340.6 / 265.0
345.5 / 291.6
355.8 / 343.0
Declared Power Input D
D
kW
45.4 / 52.1
34.2 / 39.1
27.0 / 34.0
28.8 / 41.1
Declared EER
DC,D
9.95 / 6.80
9.96 / 6.78
12.82 / 8.58
12.35 / 8.35
SSCEE
2, 3, 5
%
180
178
186
182
SSCEE Tier
Tier 2 (2021)
Tier 1 (2018)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
566.40
427.20
433.40
446.30
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
565.70
426.60
432.70
445.60
Declared EER
d
35°C
3.19
3.23
3.21
3.18
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
625.5 / 525.4
471.5 / 395.0
405.7 / 334.0
418.7 / 302.0
Declared EER
d
30°C
4.30 / 4.39
4.36 / 4.44
4.44 / 4.63
4.38 / 4.65
Declared Cooling Capacity
25°C Pdc
kW
569.7 / 459.7
427.6 / 344.7
439.2 / 359.6
451.1 / 323.0
Declared EER
d
25°C
5.72 / 5.88
5.78 / 5.93
5.95 / 6.13
5.91 / 6.08
Declared Cooling Capacity
20°C Pdc
kW
451.9 / 354.7
340.6 / 265.0
345.5 / 291.6
355.8 / 343.0
Declared EER
d
20°C
9.95 / 6.80
9.96 / 6.78
12.82 / 8.58
12.35 / 8.35
Sound Power Level L
dB(A)
86.41
86.43
86.96
87.49
Air fl ow rate
m³/h
201476.30
172693.97
156881.71
156881.71
Off mode P
OFF
0.14
0.14
0.08
0.08
Thermostat-off mode P
TO
3.17
2.59
3.53
3.80
Standby Mode P
SB
0.28
0.27
0.15
0.15
Crankcase heater mode P
CK
0.00
0.00
0.13
0.11
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
147
Chillers
DeltaChill
TM