Technical Data
Ecodesign - DCF (RQ)
Notes Units
DCF084TR-14RXYY
DCF071TR-15RXXX
DCF078TR-16RXXY
DCF091TR-15R
YYY
SEPR
1, 3, 5
6.13
6.36
6.35
5.97
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
936280.59
758620.01
841242.42
1021108.57
Rated Refrigerant Capacity P
A
1, 3, 5
kW
774.00
651.20
720.70
822.90
Rated Power Input D
A
kW
263.27
207.39
230.99
284.74
Rated EER
DC,A
2.94
3.14
3.12
2.89
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
751.9 / 653.3
638.6 / 561.5
692.1 / 614.2
806.2 / 709.2
Declared Power Input D
B
kW
187.9 / 159.4
149.2 / 128.8
162.0 / 141.4
205.6 / 177.2
Declared EER
DC,B
4.00 / 4.10
4.28 / 4.36
4.27 / 4.34
3.92 / 4.00
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
707.4 / 624.4
608.7 / 525.2
665.2 / 580.9
766.5 / 661.5
Declared Power Input D
C
kW
132.4 / 114.4
106.9 / 90.0
117.5 / 100.4
147.0 / 123.4
Declared EER
DC,C
5.34 / 5.46
5.69 / 5.84
5.66 / 5.78
5.21 / 5.36
Declared Refrigerant Capacity
P
D
kW
618.4 / 536.4
520.3 / 454.5
575.8 / 486.4
657.5 / 575.7
Declared Power Input D
D
kW
73.1 / 79.9
62.2 / 64.8
68.3 / 69.5
80.6 / 87.6
Declared EER
DC,D
8.46 / 6.71
8.37 / 7.01
8.42 / 7.00
8.16 / 6.57
SSCEE
2, 3, 5
%
163
177
174
164
SSCEE Tier
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
774.90
652.00
721.40
823.70
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
774.00
651.20
720.70
822.90
Declared EER
d
35°C
2.94
3.14
3.12
2.89
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
751.9 / 653.3
638.6 / 561.5
692.1 / 614.2
806.2 / 709.2
Declared EER
d
30°C
4.00 / 4.10
4.28 / 4.36
4.27 / 4.34
3.92 / 4.00
Declared Cooling Capacity
25°C Pdc
kW
707.4 / 624.4
608.7 / 525.2
665.2 / 580.9
766.5 / 661.5
Declared EER
d
25°C
5.34 / 5.46
5.69 / 5.84
5.66 / 5.78
5.21 / 5.36
Declared Cooling Capacity
20°C Pdc
kW
618.4 / 536.4
520.3 / 454.5
575.8 / 486.4
657.5 / 575.7
Declared EER
d
20°C
8.46 / 6.71
8.37 / 7.01
8.42 / 7.00
8.16 / 6.57
Sound Power Level L
dB(A)
91.79
89.59
89.89
91.98
Air fl ow rate
m³/h
298134.27
319429.57
340724.88
319429.57
Off mode P
OFF
0.15
0.15
0.15
0.15
Thermostat-off mode P
TO
5.46
3.87
4.32
5.13
Standby Mode P
SB
0.33
0.33
0.34
0.33
Crankcase heater mode P
CK
0.00
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.