Technical Data
Ecodesign - DCF (RQ)
Notes Units
DCF053DR-09MXY0
DCF061DR-10MYY0
DCF063DR-10MYV0
DCF047DR-12LXX0
SEPR
1, 3, 5
6.14
6.11
6.06
6.37
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
597035.99
679169.39
713335.13
498387.62
Rated Refrigerant Capacity P
A
1, 3, 5
kW
494.60
560.30
583.80
428.80
Rated Power Input D
A
kW
168.23
191.23
203.41
133.58
Rated EER
DC,A
2.94
2.93
2.87
3.21
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
543.7 / 445.2
615.4 / 516.4
643.2 / 536.1
470.7 / 394.2
Declared Power Input D
B
kW
138.2 / 109.7
157.3 / 128.6
166.9 / 134.6
108.9 / 89.5
Declared EER
DC,B
3.93 / 4.06
3.91 / 4.02
3.85 / 3.98
4.32 / 4.40
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
482.3 / 399.3
558.8 / 451.6
578.6 / 470.4
426.4 / 343.7
Declared Power Input D
C
kW
91.2 / 73.2
106.9 / 83.1
111.7 / 87.7
74.2 / 58.1
Declared EER
DC,C
5.29 / 5.45
5.23 / 5.44
5.18 / 5.36
5.75 / 5.92
Declared Refrigerant Capacity
P
D
kW
395.0 / 301.1
447.6 / 354.6
466.3 / 365.3
342.4 / 264.9
Declared Power Input D
D
kW
46.5 / 44.9
52.8 / 53.2
55.1 / 55.2
41.8 / 38.6
Declared EER
DC,D
8.49 / 6.71
8.47 / 6.67
8.46 / 6.61
8.20 / 6.86
SSCEE
2, 3, 5
%
164
167
164
178
SSCEE Tier
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
495.30
561.00
584.50
429.40
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
494.60
560.30
583.80
428.80
Declared EER
d
35°C
2.94
2.93
2.87
3.21
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
543.7 / 445.2
615.4 / 516.4
643.2 / 536.1
470.7 / 394.2
Declared EER
d
30°C
3.93 / 4.06
3.91 / 4.02
3.85 / 3.98
4.32 / 4.40
Declared Cooling Capacity
25°C Pdc
kW
482.3 / 399.3
558.8 / 451.6
578.6 / 470.4
426.4 / 343.7
Declared EER
d
25°C
5.29 / 5.45
5.23 / 5.44
5.18 / 5.36
5.75 / 5.92
Declared Cooling Capacity
20°C Pdc
kW
395.0 / 301.1
447.6 / 354.6
466.3 / 365.3
342.4 / 264.9
Declared EER
d
20°C
8.49 / 6.71
8.47 / 6.67
8.46 / 6.61
8.20 / 6.86
Sound Power Level L
dB(A)
89.88
90.33
91.16
86.83
Air fl ow rate
m³/h
191657.74
212953.05
212953.05
255543.66
Off mode P
OFF
0.14
0.14
0.14
0.14
Thermostat-off mode P
TO
3.86
3.72
4.18
2.62
Standby Mode P
SB
0.26
0.26
0.26
0.27
Crankcase heater mode P
CK
0.00
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Technical Data
Ecodesign - DCF (RQ)
Notes Units
DCF048DR-12KSS0
DCF049DR-12KSQ0
DCF054DR-1
1MXY0
DCF061DR-12MYY0
SEPR
1, 3, 5
6.98
6.88
6.33
6.30
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
465575.94
486783.53
585918.38
666925.77
Rated Refrigerant Capacity P
A
1, 3, 5
kW
438.30
452.10
500.80
566.70
Rated Power Input D
A
kW
135.70
140.84
162.07
183.99
Rated EER
DC,A
3.23
3.21
3.09
3.08
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
481.0 / 407.5
494.8 / 421.3
550.4 / 450.3
622.9 / 522.1
Declared Power Input D
B
kW
111.3 / 91.8
115.3 / 95.8
132.8 / 105.6
151.4 / 124.1
Declared EER
DC,B
4.32 / 4.44
4.29 / 4.40
4.14 / 4.27
4.11 / 4.21
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
440.7 / 359.7
453.2 / 323.0
487.5 / 403.0
564.5 / 455.5
Declared Power Input D
C
kW
74.0 / 58.7
76.5 / 53.3
87.8 / 70.8
103.1 / 80.4
Declared EER
DC,C
5.96 / 6.12
5.92 / 6.06
5.55 / 5.70
5.48 / 5.67
Declared Refrigerant Capacity
P
D
kW
350.0 / 291.6
361.0 / 343.0
399.9 / 301.1
452.7 / 354.6
Declared Power Input D
D
kW
35.3 / 34.1
36.9 / 41.2
46.8 / 44.1
53.1 / 52.2
Declared EER
DC,D
9.92 / 8.55
9.78 / 8.33
8.54 / 6.83
8.52 / 6.79
SSCEE
2, 3, 5
%
185
181
171
174
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
439.00
452.90
501.50
567.40
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
438.30
452.10
500.80
566.70
Declared EER
d
35°C
3.23
3.21
3.09
3.08
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
481.0 / 407.5
494.8 / 421.3
550.4 / 450.3
622.9 / 522.1
Declared EER
d
30°C
4.32 / 4.44
4.29 / 4.40
4.14 / 4.27
4.11 / 4.21
Declared Cooling Capacity
25°C Pdc
kW
440.7 / 359.7
453.2 / 323.0
487.5 / 403.0
564.5 / 455.5
Declared EER
d
25°C
5.96 / 6.12
5.92 / 6.06
5.55 / 5.70
5.48 / 5.67
Declared Cooling Capacity
20°C Pdc
kW
350.0 / 291.6
361.0 / 343.0
399.9 / 301.1
452.7 / 354.6
Declared EER
d
20°C
9.92 / 8.55
9.78 / 8.33
8.54 / 6.83
8.52 / 6.79
Sound Power Level L
dB(A)
87.78
88.34
88.24
88.63
Air fl ow rate
m³/h
255543.66
255543.66
234248.35
255543.66
Off mode P
OFF
0.08
0.08
0.14
0.14
Thermostat-off mode P
TO
3.64
3.93
3.60
3.40
Standby Mode P
SB
0.15
0.15
0.27
0.27
Crankcase heater mode P
CK
0.13
0.11
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
134
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020