Air C
oo
led
35
DeltaChill Technical Manual 9758541 V1.1_06_2020
Chillers
DeltaChill
TM
Technical Data
DCC Regular Quiet
Mechanical Data
Notes Units
DCC01
1DR-
04JBC0
DCC016DR-
04JGG0
DCC021DR-
04JJK0
DCC026DR-
04KKL0
DCC01
1DR-
06JBC0
DCC016DR-
06JGG0
Capacity
Number of Refrigeration Circuits
2
2
2
2
2
2
Cooling Duty - EC Fans
(1)
kW
106.5
153.1
204.4
258.3
108.2
156.2
Nominal Input - Mechanical
kW
29.8
49.0
66.4
87.5
28.4
46.0
EER
(2)
3.57
3.12
3.08
2.95
3.82
3.39
ESEER (Gross)
4.87
4.65
4.64
4.40
5.24
5.01
ESEER (Net)
4.79
4.55
4.52
4.26
5.15
4.89
Nominal Output - Free Cooling
kW
N/A
N/A
N/A
N/A
N/A
N/A
Ambient temperature for 100% Free Cooling (5)
°C
N/A
N/A
N/A
N/A
N/A
N/A
Capacity Steps
%
43-100
27-54-77-100 23-55-74-100 25-55-76-100
43-100
27-54-77-100
Minimum Turndown Ratio
0.43
0.27
0.23
0.25
0.43
0.27
Dimensions (HxW)
mm
2612x2200
2620x2200
Length
mm
2554
2554
2554
2554
3690
3690
Machine Weight
(3)
kg
1510
1650
1805
1905
1935
2075
Operating Weight
kg
1535
1680
1840
1965
1970
2115
Evaporator
Brazed Plate
Water Volume (Total Internal)
l
9.12
12.48
17.8
28.8
9.1
12.5
Maximum Waterfl ow
l/s
9.37
13.37
17.7
21.6
9.6
13.8
Minimum Waterfl ow
l/s
3.21
4.00
4.9
5.3
3.2
4.0
Condenser
Face Area (Total)
m²
9.50
9.50
9.50
9.50
14.25
14.25
Nominal Airfl ow
m³/s
25.89
25.89
25.89
25.89
38.83
38.83
Condenser Fan & Motor
Quantity
4
4
4
4
6
6
Diameter
mm
800
800
800
800
800
800
Maximum Speed
rpm
1026
1026
1026
1026
1026
1026
Compressor
Single
Tandem
Tandem
Tandem
Single
Tandem
Quantity of Compressors
2
4
4
4
2
4
Oil Charge Volume (Total)
l
1x3.6 + 1x6.1
2x3.3 +
2x3.3
2x3.6 + 2x6.1 2x6.1 + 2x6.1 1x3.6 + 1x6.1 2x3.3 + 2x3.3
Oil Type
Polyol Ester
Refrigeration
GWP Equivalent CO
2
Tonnes
tCO
2
18.23
18.90
20.93
24.98
25.65
25.65
Charge (Total)
kg
13 + 14
14 + 14
15 + 16
18 + 19
19 + 19
19 + 19
Maximum Allowable Pressure High Side (PS)
barg
40.2
40.2
40.2
40.2
40.2
40.2
Maximum Allowable Pressure Low Side (PS)
barg
29.0
29.0
29.0
29.0
29.0
29.0
Connections
Water Inlet / Outlet - Unit
DN80
DN80
DN80
DN100
DN80
DN80
Water System
Minimum System Water Volume
(4)
l
780.81
713.88
812.93
1112.09
792.43
723.82
Nominal Water Flow
l/s
5.07
7.28
9.73
12.29
5.15
7.44
Pressure drop
kPa
12.38
15.62
18.22
24.80
12.85
16.39
Electrical Data
Nominal Run Amps
(6)
A
107.8
143.6
162.8
204.3
116.4
152.2
Maximum Start Amps
A
243
302
354
395
252
310
Recommended Mains Fuse Size
A
125
160
200
250
125
200
Recommended Permanent Fuse Size
A
16
16
16
16
16
16
Maximum Permanent Incoming Cable Size
mm²
4
4
4
4
4
4
Evaporator Heater Rating
W
80
80
100
100
80
80
Condenser Fan - Per Fan (EC)
Full Load Amps
A
4.3
4.3
4.3
4.3
4.3
4.3
Motor Rating
kW
1.94
1.94
1.94
1.94
1.94
1.94
Compressor - Per Compressor
Nominal Run Amps
A
22.6 / 22.6
26.0 / 32.9
32.9 / 39.9
39.9 / 32.9
22.6 / 22.6
26.0 / 32.9
Quantity
(7)
2
2
2
2
2
2
Motor Rating
kW
13.4 / 13.4
14.7 / 19.8
19.8 / 23.8
23.8 / 19.8
13.4 / 13.4
14.7 / 19.8
Start Amps
(8)
A
158 / 158
197 / 191
191 / 231
231 / 191
158 / 158
197 / 191
(1)
Based on AC units performance at 12/7°C return/supply temperatures, 35°C ambient, 100% water. All performance data is supplied in accordance
with BS EN 14511-1:2018.
(2)
EER = DX Cooling Output / (Compressor input power + Fan Input Power).
(3)
Based on standard unit without options, operating weight includes refrigerant charge and water volume. For unit weights with waterside options fi tted
please refer to Airedale.
(4)
For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5)
Ambient temperature that full Freecool capacity can be achieved.
(6)
EC fans and no pumps.
(7)
Data quoted at design fl ow-rate, 7°C supply temperature and 35°C ambient, 100% water.
(8)
Starting amps refers to the direct on line connections.
Pump electrical data is available from Airedale upon request.
Technical Data
DCC Regular Quiet
Mechanical Data
Notes Units
DCC021DR-
06JJK0
DCC027DR-
06KKL0
DCC032DR-
06KLR0
DCC036DR-
06KRR0
DCC022DR-
08JJK0
DCC027DR-
08KKL0
Capacity
Number of Refrigeration Circuits
2
2
2
2
2
2
Cooling Duty - EC Fans
(1)
kW
209.2
266.9
322.1
355.4
212.1
271.4
Nominal Input - Mechanical
kW
62.3
81.8
103.7
117.7
59.8
78.3
EER
(2)
3.36
3.26
3.11
3.02
3.55
3.47
ESEER (Gross)
5.02
4.78
4.69
4.74
5.26
5.04
ESEER (Net)
4.87
4.62
4.53
4.56
5.09
4.86
Nominal Output - Free Cooling
kW
N/A
N/A
N/A
N/A
N/A
N/A
Ambient temperature for 100% Free Cooling (5)
°C
N/A
N/A
N/A
N/A
N/A
N/A
Capacity Steps
%
23-54-74-100 25-54-75-100 25-45-66-84-
100
19-38-54-70-
85-100
23-54-74-100 25-54-75-100
Minimum Turndown Ratio
0.23
0.25
0.25
0.19
0.23
0.25
Dimensions (HxW)
mm
2620x2200
Length
mm
3690
3690
3690
3690
4820
4820
Machine Weight
(3)
kg
2230
2335
2495
2640
2635
2745
Operating Weight
kg
2275
2410
2575
2725
2685
2830
Evaporator
Brazed Plate
Water Volume (Total Internal)
l
17.76
28.80
33.3
37.8
17.8
28.8
Maximum Waterfl ow
l/s
18.38
22.91
27.3
29.9
18.7
23.3
Minimum Waterfl ow
l/s
4.86
5.32
6.0
6.5
4.9
5.3
Condenser
Face Area (Total)
m²
14.25
14.25
14.25
14.25
19.00
19.00
Nominal Airfl ow
m³/s
38.83
38.83
38.83
38.83
51.77
51.77
Condenser Fan & Motor
Quantity
6
6
6
6
8
8
Diameter
mm
800
800
800
800
800
800
Maximum Speed
rpm
1026
1026
1026
1026
1026
1026
Compressor
Tandem
Tandem
Trio
Trio + Trio
Tandem
Tandem
Quantity of Compressors
4
4
5
6
4
4
Oil Charge Volume (Total)
l
2x3.6 + 2x6.1
2x6.1 +
2x6.1
2x6.1 + 3x6.1 3x6.1 + 3x6.1 2x3.6 + 2x6.1 2x6.1 + 2x6.1
Oil Type
Polyol Ester
Refrigeration
GWP Equivalent CO
2
Tonnes
tCO
2
27.68
32.40
35.78
36.45
35.78
39.83
Charge (Total)
kg
20 + 21
24 + 24
26 + 27
27 + 27
26 + 27
29 + 30
Maximum Allowable Pressure High Side (PS)
barg
40.2
40.2
40.2
40.2
40.2
40.2
Maximum Allowable Pressure Low Side (PS)
barg
29.0
29.0
29.0
29.0
29.0
29.0
Connections
Water Inlet / Outlet - Unit
DN80
DN100
DN100
DN100
DN80
DN100
Water System
Minimum System Water Volume
(4)
l
825.68
1133.47
1355.11
1146.12
833.12
1145.78
Nominal Water Flow
l/s
9.95
12.70
15.33
16.91
10.09
12.92
Pressure drop
kPa
19.37
26.72
30.92
30.96
19.88
27.56
Electrical Data
Nominal Run Amps
(6)
A
171.4
212.9
223.1
273.9
180.0
221.5
Maximum Start Amps
A
362
404
381
465
371
413
Recommended Mains Fuse Size
A
200
250
250
315
200
250
Recommended Permanent Fuse Size
A
16
16
16
16
16
16
Maximum Permanent Incoming Cable Size
mm²
4
4
4
4
4
4
Evaporator Heater Rating
W
100
100
100
100
100
100
Condenser Fan - Per Fan (EC)
Full Load Amps
A
4.3
4.3
4.3
4.3
4.3
4.3
Motor Rating
kW
1.94
1.94
1.94
1.94
1.94
1.94
Compressor - Per Compressor
Nominal Run Amps
A
32.9 / 39.9
39.9 / 32.9
32.9 / 32.9
39.9 / 39.9
32.9 / 39.9
39.9 / 32.9
Quantity
(7)
2
2
2
2
2
2
Motor Rating
kW
19.8 / 23.8
23.8 / 19.8
19.8 / 19.8
23.8 / 23.8
19.8 / 23.8
23.8 / 19.8
Start Amps
(8)
A
191 / 231
231 / 191
191 / 191
231 / 231
191 / 231
231 / 191
(1)
Based on AC units performance at 12/7°C return/supply temperatures, 35°C ambient, 100% water. All performance data is supplied in accordance
with BS EN 14511-1:2018.
(2)
EER = DX Cooling Output / (Compressor input power + Fan Input Power).
(3)
Based on standard unit without options, operating weight includes refrigerant charge and water volume. For unit weights with waterside options
fi tted please refer to Airedale.
(4)
For minimum system volume, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5)
Ambient temperature that full Freecool capacity can be achieved.
(6)
EC fans and no pumps.
(7)
Data quoted at design fl ow-rate, 7°C supply temperature and 35°C ambient, 100% water.
(8)
Starting amps refers to the direct on line connections.