Technical Data
Ecodesign - DCF (RQ)
Notes Units
DCF012DR-04JBC0
DCF017DR-04JGG0
DCF012DR-06JBC0
DCF018DR-06JGG0
SEPR
1, 3, 5
6.79
6.63
6.47
6.93
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
116630.98
172047.00
124627.19
168193.09
Rated Refrigerant Capacity P
A
1, 3, 5
kW
106.90
153.90
108.80
157.30
Rated Power Input D
A
kW
30.90
51.13
29.25
47.81
Rated EER
DC,A
3.46
3.01
3.72
3.29
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
117.2 / 50.0
168.4 / 129.0
119.2 / 50.8
171.9 / 131.4
Declared Power Input D
B
kW
24.9 / 10.3
41.2 / 30.4
23.3 / 9.7
38.1 / 28.2
Declared EER
DC,B
4.71 / 4.85
4.08 / 4.25
5.12 / 5.26
4.52 / 4.66
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
126.8 / 54.2
138.4 / 95.3
128.9 / 55.0
140.9 / 96.6
Declared Power Input D
C
kW
19.5 / 8.0
24.3 / 16.0
17.9 / 7.4
22.2 / 14.8
Declared EER
DC,C
6.50 / 6.75
5.70 / 5.97
7.20 / 7.40
6.35 / 6.51
Declared Refrigerant Capacity
P
D
kW
85.2 / 57.9
122.8 / 100.7
86.8 / 58.7
125.5 / 101.9
Declared Power Input D
D
kW
10.4 / 10.8
12.8 / 12.9
13.5 / 12.6
13.8 / 11.8
Declared EER
DC,D
8.17 / 5.35
9.57 / 7.81
6.42 / 4.65
9.10 / 8.62
SSCEE
2, 3, 5
%
183
174
199
189
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
107.10
154.20
109.00
157.60
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
106.90
153.90
108.80
157.30
Declared EER
d
35°C
3.46
3.01
3.72
3.29
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
117.2 / 50.0
168.4 / 129.0
119.2 / 50.8
171.9 / 131.4
Declared EER
d
30°C
4.71 / 4.85
4.08 / 4.25
5.12 / 5.26
4.52 / 4.66
Declared Cooling Capacity
25°C Pdc
kW
126.8 / 54.2
138.4 / 95.3
128.9 / 55.0
140.9 / 96.6
Declared EER
d
25°C
6.50 / 6.75
5.70 / 5.97
7.20 / 7.40
6.35 / 6.51
Declared Cooling Capacity
20°C Pdc
kW
85.2 / 57.9
122.8 / 100.7
86.8 / 58.7
125.5 / 101.9
Declared EER
d
20°C
8.17 / 5.35
9.57 / 7.81
6.42 / 4.65
9.10 / 8.62
Sound Power Level L
dB(A)
79.75
81.66
79.13
79.58
Air fl ow rate
m³/h
85181.22
85181.22
127771.83
127771.83
Off mode P
OFF
0.08
0.08
0.08
0.08
Thermostat-off mode P
TO
0.48
0.94
0.44
0.89
Standby Mode P
SB
0.11
0.11
0.12
0.12
Crankcase heater mode P
CK
0.04
0.09
0.04
0.09
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
130
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020