74
ARTUS™ Technical Manual 9690348 v3_04_2020
M
ai
nt
enan
ce
Maintenance
Drain Tray Removal
The condensate drainage system should be flushed clean of dirt and debris and condensate pumps cleaned and
inspected. The condensate drain trays should be cleaned to minimise any build up of bacteria. When cleaning the coil
and/or the condensate tray, remove the condensate drain connection to prevent debris from entering the condensate
pump. We recommend dilute soapy water (washing up liquid). Ensure the condensate pump filter is clean. If chemical
cleaners are used, ensure that both the coil and drain tray are flushed with clean water before re-connecting the drain
connection. Chemicals such as acetone or bleach should not be used.
1.
Remove push fit hose from drip tray spigots either side prior to removing tray (be aware the drip tray could contain
condensate).
2. Engage snap barbs at either end of drip tray to remove from coil end plates.
3. Manipulate the tray from the front locating lugs to drop the drip tray out from the unit / ceiling void.
4.
Clean thoroughly, refit and ensure hoses are fitted to either side of the drip tray securely on the spigots.
ARTUS™
Comfort
ARTUS™
Comfort