Commissioning
Commissioning
Pressure Independent Control Valve (PICV)
The valve is factory set to position 9.
Flow adjustment
To set the selected flow, rotate the dial on the valve to the desired position. Line up the desired preset position to the
indicator mark on the valve body.
DN15 (Heating)
DN20 (Std Cooling)
DN15 (Low-Flow Cooling)
Presetting
Pos
Max Flowrate
Max Flowrate
Max Flowrate
l/h
l/s
l/h
l/s
l/h
l/s
0
0
0
0
0
0
0
0.5
32
0.009
45
0.013
9
0.003
1
53
0.015
154
0.043
19
0.005
2
94
0.026
278
0.077
39.5
0.011
3
135
0.038
359
0.100
55
0.015
4
179
0.050
442
0.123
71
0.020
5
219
0.061
564
0.157
85
0.024
6
281
0.078
678
0.188
99.5
0.028
7
358
0.099
782
0.217
114
0.032
8
408
0.113
897
0.249
133.5
0.037
9
450
0.125
1000
0.278
150
0.042
Q
P1 - P2
35 KPa
b) START UP PRESSURE
Q≠ CONST
Q= CONST
If P1-P2 >35kPa then the valve
is within the working range
Presetting Position Dial