60
ARTUS™ Technical Manual 9690348 v3_04_2020
Ins
ta
lla
tio
n
Installation
Interconnecting Wiring
Electrical Connections
●
A fused and isolated electrical supply of the appropriate phase, frequency and voltage should be installed by the
customer.
●
As standard the product is for an electrical supply of 230V, 1 Phase, 50Hz.
●
All mains wiring and control wiring between units should be carried out to national and local codes and should be
capable of carrying the maximum load current under non-fault conditions at the stipulated voltages.
●
The electrical supply can be plugged into the socket at the side of the machine.
AR - E
L
X1
PE
Mains Incoming 230V / 1Ph + N / 50Hz/60Hz
N
X3
1
Return Air Temperature Sensor
2
To Unit (Supplied Loose)
X6
1
+
KNX / PL-Link Bus Communication Connection
2
-
Room Operator Unit
(Optional, Supplied Loose)
X2
1
Ethernet RJ45
BACnet/IP 2 Port Ethernet Switch
2
AR - M
L
X1
PE
Mains Incoming 230V / 1Ph + N / 50Hz/60Hz
N
X3
1
Return Air Temperature Sensor
2
To Unit (Supplied Loose)
X6
1
+
KNX / PL-Link Bus Communication Connection
2
-
Room Operator Unit
(Optional, Supplied Loose)
X2
1
GND
2
-
MS/TP Connection
3
+
BACnet MS/TP Connections
BACnet Ethernet Connections
Note: Shielded Cat 5e cable is recommended for Ethernet connections.
Room Sensor (optional)
Passive sensors for acquiring the temperature in the room instead of the return air temperature sensor in the ceiling
void. The room sensor is to be positioned on an inner wall of the space to be treated. It must not be obstructed by items
such as recesses, shelves, curtains etc. and must not be opposite or near heat sources (both hot or cold). The unit must
not be exposed to direct sunlight or draughts.
The room sensor shall be wired back to the unit and replaces the unit’s return air temperature sensor. To install, simply
unwire the factory return air temperature sensor with the tool provided and replace with the 2 core cable from the room
sensor. There is a grommeted hole on the side of the unit adjacent to the connection points where the cable can be fed
into the unit. Do not coil excess cable within the unit.
ARTUS™
Comfort